2006-08-24 00:00:00******DENIED******
 REFERENCE: FBC-2004 SEC. 424.2 OR
 FBRC-2004 SEC.4101 SWIMMING POOLS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1) FBC-2004 SEC. 424.6.6 OR FBC-2004
 RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. PLEASE
 SUBMIT AN ENGINEERED TABLE FOR "VENT
 PIPE MAXIMUM LENGTH" INDICATING PUMP
 SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH
 OF THE 1" PVC VENT PIPE, FROM WHERE IT
 STARTS TO WHERE IT ENDS UP, COMPLYING
 WITH THE THREE SECOND RELEASE.
 2) PLEASE SUBMIT MANUFACTURER CUT SHEETS
 OF THE CLEANING FITTING OR PLEASE ADD
 THE MAKE AND MODEL NUMBER TO THE PRINTS
 PER FBC-2004 SEC. 424.2.6.6.5 AND
 R4101.6.6.5.
  
 END OF COMMENTS:
  