Plan Review Notes For Permit 06081117 |
Permit Number |
06081117 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-24 00:00:00 | ******DENIED****** | | REFERENCE: FBC-2004 SEC. 424.2 OR | | FBRC-2004 SEC.4101 SWIMMING POOLS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR PLUMBING PLAN REVIEW: | | | | 1) FBC-2004 SEC. 424.6.6 OR FBC-2004 | | RESIDENTIAL SEC. R4101.6.6: ENTRAPMENT | | PROTECTION FOR SUCTION INLETS. PLEASE | | SUBMIT AN ENGINEERED TABLE FOR "VENT | | PIPE MAXIMUM LENGTH" INDICATING PUMP | | SIZES, AVERAGE FLOW, AND MAXIMUM LENGTH | | OF THE 1" PVC VENT PIPE, FROM WHERE IT | | STARTS TO WHERE IT ENDS UP, COMPLYING | | WITH THE THREE SECOND RELEASE. | | 2) PLEASE SUBMIT MANUFACTURER CUT SHEETS | | OF THE CLEANING FITTING OR PLEASE ADD | | THE MAKE AND MODEL NUMBER TO THE PRINTS | | PER FBC-2004 SEC. 424.2.6.6.5 AND | | R4101.6.6.5. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 | | | | |
|