2007-06-18 10:49:15REVISION: WATER HEATER TO BE FUTURE.
  
 ******PROVISO******
 A) FBC-2004 FUEL GAS SEC. 404.12 OUTLET
 CLOSURES: GAS OUTLETS THAT DO NOT CON-
 NECT TO APPLIANCES SHALL BE CAPPED GAS
 TIGHT.
 B) PER FBC-2004 FUEL GAS, SEC. 623.1,
 AND PER FBC-2004 MECHANICAL, SEC.917.1,
 COOKING APPLIANCES: COOKING APPLIANCES
 THAT ARE DESIGNED FOR PERMANENT
 INSTALLATION, INCLUDING RANGES, OVENS,
 STOVES, BROILERS, GRILLS, FRYERS,
 GRIDDLES AND BARBEQUES, SHALL BE LISTED,
 LABELED AND INSTALLED IN ACCORDANCE WITH
 THE MANUFACTURER'S INSTALLATION INSTRUC-
 TIONS.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,000 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 3,750 CUBIC FEET REQUIRED.