2007-04-12 08:45:07 | | | | | REVISION DENIED/INCOMPLETE INFORMATION | | | | 1} THERE ARE TWO METERS SHOWN ON THIS REVISION. REDRAW | | THE PLAN TO INDICATE SITE CONDITIONS. | | | | 2} THE ATS IS NOW BEING SHOWN AS FED FROM THE METER, | | AND NOW BECOMES SERVICE EQUIPMENT. PROVIDE THE AIC | | RATING OF THIS SWITCH : PER 110.9 AND 110.10: OBTAIN | | THE | | AVAILABLE FAULT CURRENT AT THE UTILITY | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | INDICATE THE AIC RATING FOR THE | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | THE AVAILABLE FAULT. | | | | 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH, | | INDICATING NUMBER OF POLES, AND HOW BOTH GENERATOR AND | | UTILITY POWER SOURCE CAN BE DISCONNECTED. | | | | 4} PLEASE SUBMIT A SITE PLAN AND LOCATE ALL | | THE SERVICE AND GENERATOR GEAR ON SAME | | SO THAT COMPLIANCE WITH | | 230.72(GROUPING), 225.31-39 FOR THE | | DISCONNECTING MEANS REQUIREMENTS AND | | 250.32 FOR GROUNDING CAN BE REVIEWED. | | | | 5} THE ATS IS SHOWN IN A PVC BOX. DEPENDING ON HOW | | ACCESSIBLE THE DISCONNECTING MEANS ARE, THIS MAY NOT BE | | ALLOWED. PLEASE EXPLAIN THE PURPOSE OF THE PVC BOX. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] |
|