Plan Review Notes
Plan Review Notes For Permit 06080658
Permit Number 06080658
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-12 08:45:07 
  
 REVISION DENIED/INCOMPLETE INFORMATION
  
 1} THERE ARE TWO METERS SHOWN ON THIS REVISION. REDRAW
 THE PLAN TO INDICATE SITE CONDITIONS.
  
 2} THE ATS IS NOW BEING SHOWN AS FED FROM THE METER,
 AND NOW BECOMES SERVICE EQUIPMENT. PROVIDE THE AIC
 RATING OF THIS SWITCH : PER 110.9 AND 110.10: OBTAIN
 THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH,
 INDICATING NUMBER OF POLES, AND HOW BOTH GENERATOR AND
 UTILITY POWER SOURCE CAN BE DISCONNECTED.
  
 4} PLEASE SUBMIT A SITE PLAN AND LOCATE ALL
 THE SERVICE AND GENERATOR GEAR ON SAME
 SO THAT COMPLIANCE WITH
 230.72(GROUPING), 225.31-39 FOR THE
 DISCONNECTING MEANS REQUIREMENTS AND
 250.32 FOR GROUNDING CAN BE REVIEWED.
  
 5} THE ATS IS SHOWN IN A PVC BOX. DEPENDING ON HOW
 ACCESSIBLE THE DISCONNECTING MEANS ARE, THIS MAY NOT BE
 ALLOWED. PLEASE EXPLAIN THE PURPOSE OF THE PVC BOX.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]