2007-11-29 09:36:33 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| (F.S.). |
| |
| MECHANICAL REVISION |
| *** DENIED *** |
| 1) COOLING LOAD CALCULATIONS SUBMITTED ARE CALLING FOR |
| 26,339 TOTAL COOLING BTU'S. FOR SYSTEM ONE, MECHANICAL |
| PLANS SUBMITTED ARE SHOWING 33,600 TOTAL COOLING BTU'S. |
| FOR SYSTEM ONE. THE PLANS CAN ONLY CALL FOR 15% MORE |
| TOTAL BTU'S. THAN THE COOLING LOAD CAL'S.. A 2.5 TON |
| SYSTEM MAY MEET THIS REQUIREMENT, SEE ATTACHED ARI |
| PRINT OUT. SEE 2004 FBC 13-607.1.ABC.1.1. |
| |
| 2)INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT |
| SEE FAC 61G1-16.004 TITLE BLOCK. |
| A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| (2) FIRM LICENSE NUMBER. |
| (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" |
| SEE CITY WPB AMEND. 106.1.1). |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| THE DOCUMENT. |
| |
| 3) THE JOB ADDRESS MUST APPEAR ON ALL PLANS, SEE 2004 |
| WPB AMEND. 106.1.1. |
| |