2007-11-29 09:36:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 MECHANICAL REVISION
 *** DENIED ***
 1) COOLING LOAD CALCULATIONS SUBMITTED ARE CALLING FOR
 26,339 TOTAL COOLING BTU'S. FOR SYSTEM ONE, MECHANICAL
 PLANS SUBMITTED ARE SHOWING 33,600 TOTAL COOLING BTU'S.
 FOR SYSTEM ONE. THE PLANS CAN ONLY CALL FOR 15% MORE
 TOTAL BTU'S. THAN THE COOLING LOAD CAL'S.. A 2.5 TON
 SYSTEM MAY MEET THIS REQUIREMENT, SEE ATTACHED ARI
 PRINT OUT. SEE 2004 FBC 13-607.1.ABC.1.1.
  
 2)INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 SEE FAC 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 3) THE JOB ADDRESS MUST APPEAR ON ALL PLANS, SEE 2004
 WPB AMEND. 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]
  