2007-03-14 10:58:10 | BUILDING REVIEW THIRD CHECKLIST: |
| 1-A) COMPLETE TRUSS PACKAGE NEEDS TO BE REVIEWED AND |
| APPROVED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL TO |
| THIS OFFICE. |
| |
| B) TRUSS ENGINEER NEEDS TO HAVE ORIGINAL SIGNATURE |
| AND SEAL IN ALL GENERAL DETAILS SHEETS SUBMITTED WITH |
| TRUSS PACKAGE AS REQUIRED BY CHAPTER 471 FLORIDA |
| STATUTE AND SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE |
| CODE. |
| |
| 2- PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS. |
| PROVIDE KEY PLAN AND INSTALLATION SCHEDULE. SEE |
| ATTACHED SAMPLE OF INSTALLATION SCHEDULE. NEED TO |
| CLEARLY IDENTIFY SPECIFIC PANEL MOUNTING CONDITIONS, |
| DESIGN PRESSURES, EDGE DISTANCE, GLASS SEPARATION, |
| ANCHOR TYPE AND SPACING AND STRUCTURE TO BE ATTACHED TO |
| VERIFY COMPLIANCE WITH THE PROPOSED INSTALLATION. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| STORM PANEL PRODUCT APPROVAL TO BE REVIEWED AND |
| APPROVED BY DESIGNER OF RECORD. |
| |
| 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FOR: |
| A) PRECAST LINTELS.TWODIFFERENT PRODUCT |
| APPROVALS WERE SUBMITTED, BUT NONE OF THEM IS |
| ACCEPTABLE.ONE OF THEM IS NOA 03-0605.05 WHICH |
| EXPIRED ON 05/21/06. THE OTHER ONE NOA 03-0605.04 IS |
| FOR 4", 6" AND 12" ONLY. NEED TO PROVIDE CORRECT AND |
| CURRENT PRODUCT APPROVAL. |
| |
| B) SLIDING GLASS DOORS. NEED ONE WITH LEGIBLE |
| DRAWINGS.ONLY ONE COPY WAS SUBMITTED. NEED TWO |
| COPIES. |
| |
| C) ENTRY DOOR. IF USING SAME MODEL AS GARAGE SIDE |
| DOOR, THEN CLEARLY INDICATE SO. |
| |
| 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING ALL |
| PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY |
| AMENDMENTS TO FBC 2004. LETTER SUBMITTED STATINGTHAT |
| HE REVIEWED "ALL" PRODUCT APPROVALS IS NOT ACCEPTABLE. |
| THIS STATEMENT DOESN'T IDENTIFY EXACTLY WHAT PRODUCT |
| APPROVALS WERE REVIEWED. NEED TO IDENTIFY IN WRITING |
| (NOT SIGNING AND SEALING) EACH SPECIFIC PRODUCT |
| APPROVAL. |
| |
| 5- NEED TO PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| THERMA-TRU CONSTRUCTION SERIES OUTSWING DOOR NOA |
| 01-0828.10.PRODUCT APPROVAL SUBMITTED REQUIRES 2X |
| STRUCTURAL BUCK. SEE PRODUCT APPROVAL.ARCHITECT'S |
| LETTER STATES THAT HIS ENGINEER TOLD HIM THAT 2X4 BUCKS |
| ARE NOT REQUIRED. PRODUCT APPROVAL SHOWS 2XSTRUCTURAL |
| BUCK DETAIL, THEREFORE DETAIL FOR 2X STRUCTURAL BUCK |
| DETAIL ATTACHMENT IS REQUIRED.PROVIDE SUCH DETAIL. |
| SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| 6- ARCHITECT TO SPECIFY OPENING PROTECTION AS REQUIRED |
| BY SEC. R309.1. NOTE IN DRAWING 1 OF 6STATING"GAR |
| DOOR PROTECTION SHALL COMPLY WITH R309 2004 RES FBC. |
| SEE NOA"IS NOT ACCEPTABLE.ARCHITECT NEEDS TO READ |
| THIS CODE SECTION AND SPECIFY HOW IS COMPLYING WITH |
| THIS CODE SECTION. ALSO,WHICH ONE IS THE NOA |
| REFERENCED IN THIS NOTE?. |
| |
| 7- ARCHITECT'S TRUSS LOADING ON DRAWING 1 OF 6 AND |
| TRUSS LOADING SPECIFIED ON TRUSS DRAWINGS DON'T MATCH. |
| REVISE AS REQUIRED. |
| |
| 8- SHEET 5 OF 6: |
| A) ARCHITECT STATES ON REVISED ITEM 13(B) THAT |
| "(1)HTSM20 ISEQUIV TO (1)HETA20.THIS IS INCORRECT |
| THIS TWO CONNECTORS ARE NOT EQUIVALENT. SEE CATALOG. |
| REVISE AS REQUIRED. |
| |
| B) ARCHITECT TO REVIEW TRUSS DRAWINGS. CONNECTORS |
| NEED TO RESIST THE CALCULATED UPLIFT AND LATERAL LOADS. |
| REVISE ALL CONNECTORS AS REQUIRED. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| C) ARCHITECT TO REVIEW GIRDER TRUSSA-13G ABOVE |
| INTERIOR BEARING WALL AND SPECIFY CONNECTORS TO RESIST |
| LOADS AT DESIGNED BEARING POINTS.SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 9- NEED RECORDED NOTICE OF COMMENCEMENT.SEC. 713.13 |
| FLORIDA STATUTE. |
| NOTE: NOTICE OF COMMENCEMENTEXPIRESAFTER 90 DAYS OF |
| BEING RECORDED IF WORK IS NOT STARTED. |
| |