Date |
Text |
2006-12-20 16:13:33 | *** DENIED *** |
| 1) AS REQUESTED IN LAST REVIEW, ENTER ALL REQUIRED |
| INFORMATION ON ENERGY CALCULATIONS, SEE HIGH LIGHTS ON |
| ENERGY CAL'S. |
| |
| 2) EQUIPMENT LISTING ON MECHANICAL PLANS IS DIFFICULT |
| TO READ. CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY. PER 2004 FBC 106.1.1. |
| |
| 3) PLEASE SHOW ON THE MECHANICAL PLANS THE SIZE OF THE |
| RETURN AIR GRILL TO THE AIR HANDLER. |
| |
| 4) PLEASE PROVIDE FOR RETURN AIR TO BEDROOMS.BALANCED |
| RETURN AIR MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |
| . |