Plan Review Notes
Plan Review Notes For Permit 06080639
Permit Number 06080639
Review Stop B
Sequence Number 2
Notes
Date Text
2007-01-08 17:28:33BUILDING REVIEW SECOND CHECKLIST:
 1- ARCHITECT NEEDS TO PROVIDE ALL REQUIRED INFORMATION
 IN THE TITLE BLOCK AS REQUIRED BYFLORIDA
 ADMINISTRATIVE CODE SEC. 61G1-16.004.
  
 2- IMPACT FEES STAMP STATES ADDITION TO BE 166SF, WHILE
 SHEET 2 OF 6 CALLS FOR NEW LIVING AREA TO BE 1528SF.
 BRING DRAWINGS TO PALM BEACH COUNTY TO REVISE IMPACT
 FEES STAMP WITH CORRECT ADDITIONAL SQUARE FOOTAGE.
 BRING BACK RE-STAMPED DRAWINGS AND COPY OF PAID RECEIPT
 IF ADDITIONAL FEES ARE DUE.
  
 3- SPECIFY ATTIC ACCESS SIZE AS REQUIRED BY SEC. R807
 2004 FLORIDA RESIDENTIAL CODE.
  
 4- LEVEL OF ALTERATION NEEDS TO BE IDENTIFIED AS
 REQUIRED BY SEC. 301.5 OF 2004 FLORIDA EXISTING CODE.
  
 5- ARCHITECT TO SPECIFY ALL DESIGN CRITERIA AS REQUIRED
 BY SEC. R301 2004 FLORIDA RESIDENTIAL CODE. INCLUDE ALL
 DEAD LOADS, LIVE LOADS, ETC.
 ALSO, SHEET 3 OF 6 DOESN'T IDENTIFY THE BUILDING CODE
 AND SPECIFIC EDITION. IT'S ALSO MISSING THE DESIGN
 PRESSURES FOR WINDOW OPENINGS. ONLY DOORS DESIGN
 PRESSURES WERE GIVEN.
  
 6- PROVIDE TRUSS DRAWINGS COMPLETE PACKAGE REVIEWED AND
 APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION AS
 REQUIRED BY SEC. R802.10.1 2004 FLORIDA RESIDENTIAL
 CODE. SEE THIS SECTION TO MAKE SURE ALL REQUIRED
 INFORMATION IS SUBMITTED. THIS INFORMATION NO NEED TO
 BE SUBMITTED RIGHT AWAY, BUT BEFORE INSTALLATION TO
 AVOID DELAYS OR CONFLICTS.
  
 7- A) PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS.
 PROVIDE KEY PLAN AND COMPLETE INSTALLATION SCHEDULE
 (SEE ATTACHED SAMPLE) OR ANY WAY THAT WILL PROVIDE ALL
 REQUIRED INFORMATION FOR PLAN REVIEW AS SHOWN ON
 INSTALLATION SCHEDULE.SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 B) PRODUCT APPROVAL TO BE REVIEWED AND APPROVED IN
 WRITING (NOT SIGNING AND SEALING) AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- ENERGY CALCULATIONS:
 A) PROVIDE SPECIFICATIONS/CALCULATIONS SHOWINGOF
 HOW R2.5 INSULATION IS ACHIEVED ON CONCRETE SLAB.
  
 B) CEILING FANS CREDIT IS TAKEN. THEREFORE, SPECIFY
 SIZE OF CEILING FANS ON ALL ROOMS AS REQUIRED BY TABLE
 13-607.1.A.1 2004 FBC. ALL CEILINGS FANS MUST BE
 INSTALLED FOR INSPECTION.
  
 C) COMPLETE ALL INFORMATION ON TOP OF FORM.
  
 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) PRECAST LINTELS. NEED CURRENT NOA FOR 8" LINTELS.
 ONE SUBMITTED IS FOR 4", 6" AND 12" LINTELS NOT FOR 8".
 SEE PLANS FOR LINTEL SIZE SPECIFIED.
  
 B) SLIDING GLASS DOORS. SEE PLANS FOR SIZE.
  
 C) ALL STRUCTURAL CONNECTORS SPECIFIED ON TRUSS
 CONNECTOR SCHEDULE AND IN ALL DETAILS AND NOTES. SEE
 PLANS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND
 PAGE SHOWING EACH CONNECTOR ONLY. NO NEED TO SUBMIT THE
 WHOLE LONG REPORT.
  
 D) ENTRY DOOR.
  
 E) SINGLE HUNG WINDOWS. NOA 05-0112.01 SUBMITTED
 EXPIRED ON 10/08/06. NEED CURRENT ONE.
  
 F) GARAGE SIDE AND REAR DOOR. NOA 02-0805.03
 SUBMITTED IS FOR DOUBLE DOORS ONLY. NEED PRODUCT
 APPROVAL FOR SINGLE DOORS AS SHOWN ON PLANS.
  
 G) 12' WIDE X 7' HIGH GARAGE DOOR. NOA 03-0430.04
 SUBMITTED IS FOR 9' WIDE DOORS ONLY.
  
 10- ARCHITECT TO REVIEW PRODUCT APPROVAL FOR GARAGE
 SIDE AND REAR DOOR. IF PRODUCT APPROVAL REQUIRES 2X
 STRUCTURAL BUCK, THEN PROVIDE SUCH DETAIL. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 11- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT
 SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 12- SPECIFY GARAGE OPENING PROTECTION AS REQUIRED BY
 SEC. R309 2004 FLORIDA RESIDENTIAL CODE.
  
 13- SHEET 5 OF 6:
 A) SPECIFY UPLIFT LOADS AND CONNECTORS AT THE ENDS
 OF GIRDER TRUSS ABOVE INTERIOR BEARING WALL.AND,
 SPECIFY STUDS TO RECEIVE GIRDER TRUSS BY BEDROOM #3.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 B) SPECIFY TRUSS CONNECTORS FOR TRUSSES RESTING ON
 EXISTING MASONRY WALL.HETA CONNECTORS NEED TO BE
 EMBEDED IN CONCRETE. NEED RETROFIT CONNECTOR. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) SEE CURRENT SIMPSON CATALOGUE AND REVISE ALL
 SPECIFIED CONNECTORS IF NUMBER AND TYPE OF FASTENERS
 DON'T MATCH THE ONES TESTED AND PUBLISHED BY THE
 MANUFACTURER'S. OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS FOR FASTENERS THAT DIFFER FROM THOSE ALREADY
 PUBLISHED.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 SEE ALL CONNECTORS SPECIFIED THROUGHOUT THIS PAGE AND
 REVISE AS REQUIRED.CONNECTORS ARE TAKEN FROM SIMPSON
 2004 CATALOGUE AND USP 2003 CATALOGUE. UPDATE AS
 REQUIRED. SEE COMMENTS ON PLANS.
  
 D) REVISE CONNECTOR B. IT CALLS FOR (2) HETA20 AT
 EACH END OF TRUSS. THIS CONNECTOR CAN'T BE INSTALLED ON
 WOOD TO WOOD CONNECTION. ALSO, IT CAN'T BE INSTALLED ON
 EXISTING WALL. REVISE AS REQUIRED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 14- DRAWINGS SHOWREVISED SQUARE FOOTAGE AREAS.
 PERMIT VALUATION WAS UPDATED ACCORDINGLY. THEREFORE,
 OWES $542.74 FOR PERMIT VALUATION AND RADON FEES.
  
 15- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS IF
 WORK IS NOT STARTED.SEC. 713.13 FLORIDA STATUTES.
 NEED RE-RECORDED NOTICE OF COMMENCEMENT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712