2007-01-08 17:28:33 | BUILDING REVIEW SECOND CHECKLIST: |
| 1- ARCHITECT NEEDS TO PROVIDE ALL REQUIRED INFORMATION |
| IN THE TITLE BLOCK AS REQUIRED BYFLORIDA |
| ADMINISTRATIVE CODE SEC. 61G1-16.004. |
| |
| 2- IMPACT FEES STAMP STATES ADDITION TO BE 166SF, WHILE |
| SHEET 2 OF 6 CALLS FOR NEW LIVING AREA TO BE 1528SF. |
| BRING DRAWINGS TO PALM BEACH COUNTY TO REVISE IMPACT |
| FEES STAMP WITH CORRECT ADDITIONAL SQUARE FOOTAGE. |
| BRING BACK RE-STAMPED DRAWINGS AND COPY OF PAID RECEIPT |
| IF ADDITIONAL FEES ARE DUE. |
| |
| 3- SPECIFY ATTIC ACCESS SIZE AS REQUIRED BY SEC. R807 |
| 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 4- LEVEL OF ALTERATION NEEDS TO BE IDENTIFIED AS |
| REQUIRED BY SEC. 301.5 OF 2004 FLORIDA EXISTING CODE. |
| |
| 5- ARCHITECT TO SPECIFY ALL DESIGN CRITERIA AS REQUIRED |
| BY SEC. R301 2004 FLORIDA RESIDENTIAL CODE. INCLUDE ALL |
| DEAD LOADS, LIVE LOADS, ETC. |
| ALSO, SHEET 3 OF 6 DOESN'T IDENTIFY THE BUILDING CODE |
| AND SPECIFIC EDITION. IT'S ALSO MISSING THE DESIGN |
| PRESSURES FOR WINDOW OPENINGS. ONLY DOORS DESIGN |
| PRESSURES WERE GIVEN. |
| |
| 6- PROVIDE TRUSS DRAWINGS COMPLETE PACKAGE REVIEWED AND |
| APPROVED BY THE ARCHITECT PRIOR TO INSTALLATION AS |
| REQUIRED BY SEC. R802.10.1 2004 FLORIDA RESIDENTIAL |
| CODE. SEE THIS SECTION TO MAKE SURE ALL REQUIRED |
| INFORMATION IS SUBMITTED. THIS INFORMATION NO NEED TO |
| BE SUBMITTED RIGHT AWAY, BUT BEFORE INSTALLATION TO |
| AVOID DELAYS OR CONFLICTS. |
| |
| 7- A) PROVIDE COMPLETE INFORMATION FOR STORM SHUTTERS. |
| PROVIDE KEY PLAN AND COMPLETE INSTALLATION SCHEDULE |
| (SEE ATTACHED SAMPLE) OR ANY WAY THAT WILL PROVIDE ALL |
| REQUIRED INFORMATION FOR PLAN REVIEW AS SHOWN ON |
| INSTALLATION SCHEDULE.SEC. 106.1.2 CITY AMENDMENTS TO |
| FBC 2004. |
| |
| B) PRODUCT APPROVAL TO BE REVIEWED AND APPROVED IN |
| WRITING (NOT SIGNING AND SEALING) AS REQUIRED BY SEC. |
| 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 8- ENERGY CALCULATIONS: |
| A) PROVIDE SPECIFICATIONS/CALCULATIONS SHOWINGOF |
| HOW R2.5 INSULATION IS ACHIEVED ON CONCRETE SLAB. |
| |
| B) CEILING FANS CREDIT IS TAKEN. THEREFORE, SPECIFY |
| SIZE OF CEILING FANS ON ALL ROOMS AS REQUIRED BY TABLE |
| 13-607.1.A.1 2004 FBC. ALL CEILINGS FANS MUST BE |
| INSTALLED FOR INSPECTION. |
| |
| C) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| |
| 9- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FOR: |
| A) PRECAST LINTELS. NEED CURRENT NOA FOR 8" LINTELS. |
| ONE SUBMITTED IS FOR 4", 6" AND 12" LINTELS NOT FOR 8". |
| SEE PLANS FOR LINTEL SIZE SPECIFIED. |
| |
| B) SLIDING GLASS DOORS. SEE PLANS FOR SIZE. |
| |
| C) ALL STRUCTURAL CONNECTORS SPECIFIED ON TRUSS |
| CONNECTOR SCHEDULE AND IN ALL DETAILS AND NOTES. SEE |
| PLANS. PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND |
| PAGE SHOWING EACH CONNECTOR ONLY. NO NEED TO SUBMIT THE |
| WHOLE LONG REPORT. |
| |
| D) ENTRY DOOR. |
| |
| E) SINGLE HUNG WINDOWS. NOA 05-0112.01 SUBMITTED |
| EXPIRED ON 10/08/06. NEED CURRENT ONE. |
| |
| F) GARAGE SIDE AND REAR DOOR. NOA 02-0805.03 |
| SUBMITTED IS FOR DOUBLE DOORS ONLY. NEED PRODUCT |
| APPROVAL FOR SINGLE DOORS AS SHOWN ON PLANS. |
| |
| G) 12' WIDE X 7' HIGH GARAGE DOOR. NOA 03-0430.04 |
| SUBMITTED IS FOR 9' WIDE DOORS ONLY. |
| |
| 10- ARCHITECT TO REVIEW PRODUCT APPROVAL FOR GARAGE |
| SIDE AND REAR DOOR. IF PRODUCT APPROVAL REQUIRES 2X |
| STRUCTURAL BUCK, THEN PROVIDE SUCH DETAIL. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| 11- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| SIGNING AND SEALING)ALL PRODUCT APPROVALS AS REQUIRED |
| BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 12- SPECIFY GARAGE OPENING PROTECTION AS REQUIRED BY |
| SEC. R309 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 13- SHEET 5 OF 6: |
| A) SPECIFY UPLIFT LOADS AND CONNECTORS AT THE ENDS |
| OF GIRDER TRUSS ABOVE INTERIOR BEARING WALL.AND, |
| SPECIFY STUDS TO RECEIVE GIRDER TRUSS BY BEDROOM #3. |
| SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| B) SPECIFY TRUSS CONNECTORS FOR TRUSSES RESTING ON |
| EXISTING MASONRY WALL.HETA CONNECTORS NEED TO BE |
| EMBEDED IN CONCRETE. NEED RETROFIT CONNECTOR. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| C) SEE CURRENT SIMPSON CATALOGUE AND REVISE ALL |
| SPECIFIED CONNECTORS IF NUMBER AND TYPE OF FASTENERS |
| DON'T MATCH THE ONES TESTED AND PUBLISHED BY THE |
| MANUFACTURER'S. OTHERWISE, PROVIDE COMPLETE ENGINEERING |
| ANALYSIS FOR FASTENERS THAT DIFFER FROM THOSE ALREADY |
| PUBLISHED.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| SEE ALL CONNECTORS SPECIFIED THROUGHOUT THIS PAGE AND |
| REVISE AS REQUIRED.CONNECTORS ARE TAKEN FROM SIMPSON |
| 2004 CATALOGUE AND USP 2003 CATALOGUE. UPDATE AS |
| REQUIRED. SEE COMMENTS ON PLANS. |
| |
| D) REVISE CONNECTOR B. IT CALLS FOR (2) HETA20 AT |
| EACH END OF TRUSS. THIS CONNECTOR CAN'T BE INSTALLED ON |
| WOOD TO WOOD CONNECTION. ALSO, IT CAN'T BE INSTALLED ON |
| EXISTING WALL. REVISE AS REQUIRED. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 14- DRAWINGS SHOWREVISED SQUARE FOOTAGE AREAS. |
| PERMIT VALUATION WAS UPDATED ACCORDINGLY. THEREFORE, |
| OWES $542.74 FOR PERMIT VALUATION AND RADON FEES. |
| |
| 15- NOTICE OF COMMENCEMENT IS EXPIRED AFTER 90 DAYS IF |
| WORK IS NOT STARTED.SEC. 713.13 FLORIDA STATUTES. |
| NEED RE-RECORDED NOTICE OF COMMENCEMENT. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |