Plan Review Notes
Plan Review Notes For Permit 06080639
Permit Number 06080639
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-17 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE ARE PANEL SCHEDULES AND RISERS
 ON SHEET A5 AND E2, DECIDE WHICH ONE IS
 CORRECT AND REMOVE THE OTHER.
  
 2} PLEASE COMBINE ALL DRAWINGS PERTINENT
 TO THE ELECTRICAL SCOPE ON THE SAME
 SHEET OR CONTINUOUS PROGRESSION OF
 SHEETS. 106.1.3 FBC, AS AMENDED.
  
 3} SEE 220.30 FOR REQUIRED ITEMS FOR THE
 LOAD CALCULATION, INCLUDE ALL.
  
 4} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2. SEE SHEET
 E2.
  
 5} THE GARAGE RECEPTACLES ARE REQUIRED
 TO BE GFI PROTECTED PER 210.8(A)(2).
  
 6} SMOKE DETECTORS MUST BE INSTALLED TO
 COMPLY WITH R313.1 RESIDENTIAL FLORIDA
 BUILDING CODE.
  
 7} KITCHEN RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(A), 210.52(C), AND
 210.8(A)(6) GFI.
  
 8} INDICATE THE REQUIRED BATH CIRCUITS
 ON THE PANEL SCHEDULE. 210.11(C)(3).
  
 9} INDICATE THE REQUIRED ARC FUULT
 CIRCUITS ON THE PANEL SCHEDULE. 210.12.
  
 WILLIAM R TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/561) 805-6731
  