Plan Review Notes For Permit 06080639 |
Permit Number |
06080639 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-17 00:00:00 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THERE ARE PANEL SCHEDULES AND RISERS | | ON SHEET A5 AND E2, DECIDE WHICH ONE IS | | CORRECT AND REMOVE THE OTHER. | | | | 2} PLEASE COMBINE ALL DRAWINGS PERTINENT | | TO THE ELECTRICAL SCOPE ON THE SAME | | SHEET OR CONTINUOUS PROGRESSION OF | | SHEETS. 106.1.3 FBC, AS AMENDED. | | | | 3} SEE 220.30 FOR REQUIRED ITEMS FOR THE | | LOAD CALCULATION, INCLUDE ALL. | | | | 4} THE PERSON TAKING RESPONSIBILITY FOR | | THE DESIGN MUST PRINT AND SIGN THEIR | | NAME TO SAME PER 106.3.4.2. SEE SHEET | | E2. | | | | 5} THE GARAGE RECEPTACLES ARE REQUIRED | | TO BE GFI PROTECTED PER 210.8(A)(2). | | | | 6} SMOKE DETECTORS MUST BE INSTALLED TO | | COMPLY WITH R313.1 RESIDENTIAL FLORIDA | | BUILDING CODE. | | | | 7} KITCHEN RECEPTACLE SPACING MUST | | COMPLY WITH 210.52(A), 210.52(C), AND | | 210.8(A)(6) GFI. | | | | 8} INDICATE THE REQUIRED BATH CIRCUITS | | ON THE PANEL SCHEDULE. 210.11(C)(3). | | | | 9} INDICATE THE REQUIRED ARC FUULT | | CIRCUITS ON THE PANEL SCHEDULE. 210.12. | | | | WILLIAM R TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/561) 805-6731 | | |
|