2006-09-19 00:00:00BUILDING REVIEW CHECKLIST:
 1- A) ARCHITECT NEEDS TO PROVIDE ALL HIS
 INFORMATION IN THE TITLE BLOCK AS REQ'D
 BY FLORIDA ADMINISTRATIVE CODE SECTION
 61G1-16.004. SEE ATTACHED COPY.
 B) ARCHITECT NEEDS TO WRITE DOWN DATE
 WHEN SIGNING AND SEALING PLANS AS
 REQUIRED BY FLORIDA ADMINISTRATIVE CODE.
  
 2- PROVIDE COPY OF THE IMPACT FEES PAID
 RECEIPT.
  
 3- ALL BEDROOMS WINDOWS DON'T COMPLY
 WITH EGRESS REQUIREMENTS. SEC. R310 OF
 2004 RESIDENTIAL CODE.
  
 4- SITE PLAN ON SHEET A-1 IS NOT TO
 SCALE.
  
 5- A) MISSING ONE ELEVATION. PROVIDE
 EAST ELEVATION. EAST ELEVATION SHOWN ON
 PLANS CORRESPONDS TO NORTH ELEVATION.
 REVISE AS REQUIRED.
 B) ROOF SHOWN ON ELEVATIONS DON'T MATCH
 ROOF FRAMING PLAN. REVISE AS REQUIRED.
  
 6- SPECIFY ALL SIZES & TYPES OF WINDOWS
 AND GLASS BLOCK. SOME WINDOWS ARE
 MISSING THIS INFORMATION.
  
 7- SPECIFY SAFETY GLASS FOR WINDOW ABOVE
 TUB ON EAST ELEVATION. SEC. R308.4 2004
 RESIDENTIAL CODE.
  
 8- PROVIDE COMPLETE STRUCTURAL DETAIL
 SHOWING HOW ARE SLIDING GLASS DOORS AT
 FAMILY ROOM MULLED TOGETHER. AND HOW IS
 MULLION ATTACHED TO STRUCTURE AT TOP AND
 BOTTOM. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 9- PLANS ARE NOT CLEAR. NEED TO PROVIDE
 WALL LEGEND TO IDENTIFY TYPE OF WALLS,
 WHAT'S NEW, WHAT'S EXISTING AND WHICH
 WALLS ARE TO BE REMOVED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 10- PROVIDE STRUCTURAL DETAILS/SPECS
 SHOWING STRUCTURAL SUPPORT WHEN WALLS
 ARE REMOVED. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 11- PROVIDE COMPLETE AND CORRECT BEAM,
 LINTEL, COLUMN AND FOOTING SCHEDULE.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 12- PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS JOB. THERE ARE MANY DETAILS THAT
 DON'T APPLY TO THIS JOB.
 ALSO, THERE ARE SOME REPETITIVE DETAILS
 WITH INFORMATION THAT DOESN'T MATCH.
  
 13- PROVIDE DETAIL FOR STEP UP AT DINING
 ROOM. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 14- CLARIFY WHY ARE THERE NO DOORS TO
 ENTER BATHROOM ON EAST SIDE.SECTION
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 15- PROVIDE SMOKE DETECTORS IN BEDROOMS
 AS REQ'D BY SEC. R313 2004 RES. CODE.
  
 16- SPECIFY ATTIC ACCESS AS REQUIRED BY
 SEC. R807 2004 RESIDENTIAL CODE.
  
 17- ARCHITECT TO IDENTIFY LEVEL OF
 ALTERATION AS REQUIRED BY SECTION 301.5
 OF 2004FLORIDA EXISTING BUILDING CODE.
  
 18- ARCHITECT TO SPECIFY BUILDING CODE
 AND ALL DESIGN CRITERIA AS REQUIRED BY
 SEC. R301 2004 RESIDENTIAL CODE.
  
 19- PROVIDE TRUSS DRAWINGS REVIEWED AND
 APPROVED BY THE ARCHITECT PRIOR TO
 INSTALLATION AS REQUIRED BY SEC.
 R802.10.1 2004 RESIDENTIAL CODE.
  
 20- ARCHITECT TO SPECIFY CONCRETE SLAB
 JOINTS AS REQUIRED BY SECTION R506.2.4
 2004 RESIDENTIAL CODE.
  
 21- ARCHITECT TO SPECIFY CALCULATED
 DESIGN PRESSURES FOR DOORS, WINDOWS AND
 GARAGE DOOR. SEC. R301 2004 RES. CODE.
  
 22- PROVIDE COMPLETE INFORMATION FOR
 STORM SHUTTERS INCLUDING KEY PLAN AND A
 COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE OF INSTALLATION SCHEDULE
 ON CITY IMPLEMENTATION STANDARD FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION.
  
 23- PROVIDE CORRECT ENERGY CALCULATIONS.
 NEED TO COMPLETE FORM 600A-04. FORM
 600C-04 SUBMITTED IS FOR ADDITIONS OF
 600S.F. OR LESS ONLY.
  
 24- AS REQUIRED DCA RULE 9B-72, PROVIDE
 PRODUCT APPROVAL FOR:
 A) WINDOW MULLIONS. PRODUCT APPROVAL
 SUBMITTED IS EXPIRED. NEED UPDATED NOA.
 B) PRECAST LINTELS. ONE SUBMITTED IS
 FOR 4", 6" & 12". THESE LINTELS ARE NOT
 USED. NEED CURRENT NOA FOR 8" LINTELS.
 C) SLIDING GLASS DOORS.
 D) GLASS BLOCK.
 E) ALL STRUCTURAL CONNECTORS SPECIFED
 ON TRUSS ANCHOR SCHEDULE AND DETAILS.
 F) MULLION FOR SLIDING GLASS DOORS.
  
 25- ARCHITECT TO REVIEW AND APPROVE IN
 WRITTING ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 OF CITY
 AMENDMENTS TO FBC 2004.
  
 26- ACCORDING TO WALL SECTION ON SHEET
 A-5 THE ROOF PITCH IS 3:12. NEED TO
 SPECIFY DOUBLE LAYER OF UNDERLAYMENT AS
 REQ'D BY SEC. R905.27 2004 RES. CODE.
  
 27- PLEASE RETURN REVIEWED SET TO
 EXPEDITE REVIEW PROCESS.
  
 28- SPECIFY BEAM/HEADER ABOVE GLASS
 BLOCK IN DINING ROOM AND HOW IS
 STRUCTURE SUPPORTED WHILE REMOVING WALL.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 29- PLANS ARE MISSING A LOT OF
 DIMENSIONS. PROVIDE ALL DIMENSIONS
 INCLUDING DIMENSIONS BETWEEN KITCHEN AND
 FAMILY ROOM. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 30- SPECIFY GARAGE OPENING PROTECTION AS
 REQUIRED BY SEC. R309 2004 RES. CODE.
  
 31- CLARIFY IF THERE IS A STEP FROM
 GARAGE FINISH FLOOR TO INTERIOR OF HOUSE
 FINISH FLOOR. PLANS DON'T PROVIDE THIS
 INFORMATION. SECTION 106.1.2 OF CITY
 AEMNDMENTS TO FBC 2004.
  
 32. REVISE STRUCTURAL GARAGE DOOR BUCK
 DETAIL TO MATCH ACTUAL CONDITIONS. SEE
 FLOOR PLAN AND REVISE AS REQUIRED.
  
 33- SHEET A-2:
 A) THERE IS A 3'X3' CONCRETE PAD IN
 FOUNDATION PLAN. WHAT IS THIS FOR? IS
 THIS TO SUPPORT A COLUMN?. SPECIFY
 COLUMN AND CONCRETE PAD REINFORCEMENT.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 B) HOW IS BEAM AT NEW PORCH AREA
 SUPPORTED? ARE THERE ANY CONCRETE PADS
 REQUIRED TO SUPPORT CONCRETE COLUMNS?.
 PROVIDE COMPLETE INFORMATION. SECTION
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 C) SIZE OF FOOTING DOESN'T MATCH WALL
 SECTIONS. PROVIDE COMPLETE FOOTING SIZES
 FOR ALL FOOTING TYPES SHOWN ON PLAN.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 34- SPECIFY WHAT IS THE FINISH FLOOR AT
 NEW PORCH. CONCRETE? NO INFORMATION
 GIVEN. LOOK AT ELEVATIONS. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 35- SHEET A-4:
 A) ROOF FRAMING PLAN IS WRONG AND
 INCOMPLETE. SEE EXTERIOR ELEVATIONS.
 B) SPECIFY CALCULATED UPLIFT LOADS.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 C) SPECIFY ALL BEARING WALLS. SECTION
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 D) PROVIDE TRUSS ANCHOR SCHEDULE.
 E) DIMENSIONS DON'T MATCH PLANS.
  
 36- SHEET A-5:
 A) REVISE STRUCTURAL BUCK DETAILS FOR
 DOORS AND WINDOWS TO COMPLY WITH SECTION
 R613.6.2 2004 RESIDENTIAL CODE.
 B) SIZE OF FASTENER SPECIFIED FOR
 WINDOW ATTACHMENT DOESN'T WORK ACCORDING
 TO SIZE OF BUCK SPECIFIED. REVISE.
 C) NOTE AT BOTTOM OF TYPICAL WALL
 SECTION REGARDING WINDOW/DOOR BUCKS
 DON'T MATCH DETAILS SHOWN ON TOP OF
 PAGE. REVISE AS REQUIRED..
 D) SIZE OF TYPICAL WALL SECTION
 DOESN'T MATCH FOUNDATION PLAN. REVISE AS
 REQUIRED.
 E) DETAIL F: REVISE HUGHES CONNECTORS.
 THIS COMPANY IS OUT OF BUSINESS.
 F) LINTEL DETAILS. PROVIDE INFORMATION
 REGARDING THE ADDITIONAL REINFORCEMENT.
 G) SIMPSON H10 CONNECTOR SPECIFIED ON
 TYP. WALL SECTION IS FOR WOOD TO WOOD
 CONNECTION. NEED WOOD TO MASONRY
 CONNECTOR. SEE CURRENT CATALOGUE FOR
 PROPER CONNECTOR.
 H) TYP. WALL SECTION: WHAT LOCAL CODE
 CALLS FOR 2% CLORDANE SOLUTION? CLARIFY
 NOTE FOR CONCRETE SLAB.
  
 37- SHEET A-6:
 A) UPDATE ALL CONSTRUCTION DOCUMENT
 NOTES AND ALL GENERAL CONSTRUCTION
 NOTES. SEE 2004 FLORIDA BUILDING AND
 RESIDENTIAL CODES TO REFERENCE CORRECT
 CODE STANDARDS AND EDITIONS.
 B) PROVIDE INFORMATION FOR ADDITIONAL
 LINTEL REINFORCEMENTS. SEE LINTEL
 DETAILS. SEC. 106.1.2 CITY AMENDMENTS.
 C) WALL SECTION CALLS FOR SPANISH 'S'
 TILE. REVISE AS REQUIRED. ALS. THIS WALL
 SECTION DOESN'T MATCH OTHER WALL SECTION
 SHOWN ON SHEET A-5. REVISE AS REQUIRED.
  
 38- SHEET A-8:
 A) UPDATE ALL STRUCTURAL NOTES. SEE
 2004 FLORIDA BUILDING AND RESIDENTIAL
 CODES FOR CORRECT CODE STANDARDS AND
 EDITIONS. REVISE ALL NOTES AS REQUIRED
 INCLUDING DESIGN WIND LOADS AND ROOF
 LOADS.
 B) PROVIDE ONLY THE DETAILS THAT APPLY
 TO THIS JOB.
  
 39- OWES $139.57 FOR UPDATED PERMIT
 VALUATION AND RADON FEES.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712