2006-08-24 00:00:00 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE CLARIFY IF THE CONTINOUS |
| LOADS ARE SHOWN AT 125%.215.3,230.42 ETC |
| |
| 2) NOTE: PLEASE SEE FBC 2004 CHAPTER 13. |
| 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR |
| LIGHTING CONTROLS REQUIRED. |
| PLEASE PROVIDE INFORMATION FOR DEVICES. |
| IF OVER RIDES ARE TIMER TYPE (4HRS MAX) |
| IF SENSOR TYPE (30MINS MAX) PLEASE |
| INDICATE. |
| PLEASE SEE LIGHTING POWER DENSITIES. |
| 13-415.2.ABC.1, TABLES 415.2.C.1. |
| 415.2.B.1 |
| |
| |
| 3) NOTE: PLEASE BE SURE THE FOLLOWING |
| CODES AT STATED ON PLANS AT A MIN. |
| 2002 NFPA-72, 2003 NFPA-101, 2004 FBC. |
| 2002 NEC IS ALREADY ON PLANS. |
| |
| 4) NOTE: PLEASE VERIFY THE PANEL 5LL |
| CONTAINING A MCB TO MEET 240.21 AND |
| 408.16. PLEASE KNOW, IF ONE IS NOT |
| EXISTING, ONE WILL BE REQUIRED TO BE |
| INSTALLED. |
| PLEASE VERIFY. |
| |
| 5) NOTE: PLEASE SEEPLANS IN ONE SET OF |
| THE TWO ARE NOT SIGNED, DATED OR SEAL |
| FOR BOTH ELECTRICAL SHEETS, ONE |
| MECHANICAL AND THREE OF THE |
| ARCHITECTURALS. |
| PLEASE KNOW, SIGNING AND SEALING OF |
| PLANS IS REQUIRED FOR ALL TRADES AND FOR |
| ALL REVIEWER(S) WHETHER OR NOT COMMENT |
| IS MADE BY THE OTHER REVIEWER(S). |
| PLEASE SEE FS 481.221, 471.025 |
| |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |