2006-12-15 18:43:30 | BUILDING PLAN REVIEW | | PERMIT:06080556 | | ADD:3000 PRESIDENTIAL WAY | | CONT: RICK BENNET | | TEL: (561)541-227 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW : REV | | ACTION: DENIED | | | | 1)THE PRODUCT APPROVAL SUBMITTED NEEDS TO INDICATE | | WHICH ITEMS WILL BE USED TO INSTALL THE SHUTTERS. | | NOTHING ON THE PRODUCT APPROVAL HAS BEEN IDENTIFY. | | CIRCLE THE ITEMS TO BE USED. SEE PAGES 5 AND 6 FOR THE | | DIFFERENT TYPES OF WALL/FLOOR AND CEILING MOUNTING | | DETAILS AND CHOSE THE SYSTEM WHICH WILL BE USED. PAGE 9 | | HAS THE INFORMATION FOR THE GLASS SEPERATION THEN SEE | | PAGES 10 AND 11 FOR THE MAXIMUM DESIGN PRESSURES, | | ANCHOR SPACING AND SHUTTER SPAN. NOTE: ONLY THREE | | DIFFERENT TYPES OF FASTENERS CAN BE USED FROM THIS | | PRODUCT APPROVAL SEE ANCHOR SPACING LEGEND ON PAGES 10 | | AND 11 TOP LEFT HAND CORNER. THE SHUTTER MOUNTING SHOWN | | ON THE INSTALLATION SCHEDULE PROVIDED DOES NOT | | CORRESPOND WITH THE NEW PRODUCT APPROVAL. IN THE | | PACKAGE IS A SAMPLE OF AN INSATLLATION SCHEDULE EITHER | | FILL THIS ONE OUT OR PROVICE A SIMILAR SCHEDULE WITH | | ALL REQUIRED INFORMATION. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 |
|