Plan Review Notes
Plan Review Notes For Permit 06080554
Permit Number 06080554
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-30 15:32:43****** UNSAT2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING, ALSO THERE ARE SOME NEW
 NOTES BASED ON SOME CHANGES ON PLANS.
  
 1) NOTE: OK
  
 2) NOTE: NO, PLEASE STILL CLARIFY SERVICE EQUIPMENT. IS
 THIS A 300A PANEL BOARD OF SOME KIND, A 300A METER MAIN
 COMBO WITH TWO MAINS?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE PLANS AND RISER. RISER SHOWS WHAT
 APPEARS TO BE A
 300A SERVICE, YET PLANS INDICATE 200A'S.
 230.70 , 215.5, 230.2 ETC
  
 3) NOTE:NO, PLEASE SEE THE RISER DIAGRAM DOES NOT
 INDICATE ANY SERVICE ENTRANCE CONDUCTORS? PLEASE SEE
 THE CODE SECTIONS AS PREVIOUSLY NOTED WERE ADDED TO A
 NOTE #19, HOWEVER IT IS NOT PERMITTED TO PLACE CODE
 SECTIONS ON PLANS IN LIEU OF ACTUAL DETAIL OF DESIGN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER DOES NOT INDICATE ANY SEC'S . PLEASE
 COMPLETE RISER.
 310.15B6,310.16,240.4 ETC
  
 4) NOTE: OK.
  
 5) NOTE:NO, SEE NOTE #2, FOR CLARIFICATION OF SERVICE
 MAIN EQUIPMENT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE INFORMATION FOR MAIN/PANEL/DISCONNECT ON
 RISER WHICH FEEDS TWO SUB PANELS. PLEASE SEE 230.70 AS
 THERE CAN BE NO MORE THAN 6 SPACES FOR EQUIPMENT AND NO
 MORE THAN 6 MAINS FOR SERVICE.
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK; HOWEVER SEE POSSIBLE NOTE UNDER 06081932
 AS THE SAME RISER SHOULD BE NOTED UNDER THAT REVIEW.
 CABANA IS UNDER A SEPARATE PERMIT..
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: NO, PLEASE SEE CIRCUITING WHICH HAS NOW BEEN
 ADDED TO PLANS WHICH DO NOT CORRELATE WITH THE PANEL
 SCHEDULE SUBMITTED. AS PREVIOUSLY NOTED, PLEASE ONLY
 INDICATE THE AREAS WHICH ARE BEING FED FROM THE
 CIRCUITS ON PANEL SCHEDULE.
 PLEASE SEE NOW PLANS INDICATE BATH ROOM GFI"S BEING FED
 FROM THE SMALL APPLIANCE CIRCUIT(S).
 PLEASE SEE SMALL APPLIANCE CIRCUITS FEEDING BEDROOM,
 HALLWAY, LIVING ROOM ETC.
 PLEASE SEE ONLY ONE SMALL APPLIANCE CIRCUIT SHOWN IN
 KITCHEN ETC.
 PLEASE KNOW IT WAS ONLY REQUESTED TO INDICATE ON THE
 PANEL SCHEDULE THESE AREAS/ROOMS.
 PLEASE SEE THE FOLLOWING SECTIONS FOR ITEMS NOT
 PERMITTED ON SMALL APPLIANCE OR BATHROOM CIRCUITS.
 210.52B1, 210.52D, 210.11C1, 210.11C3, 220.16
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PANEL SCHEDULE FOR ALL CIRCUITS TO THE
 ROOMS AND AREAS IN WHICH THEY FEED. CIRCUITS ARE TO BE
 SPECIFIC. IE: LIVING RM, KITCHEN LTS, ETC.
 408.6.
 106.1.2
 ** IT IS KNOWN TO THIS OFFICE THAT THE CIRCUITING WILL
 BE REVISED AT A LATER DATE, HOWEVER THE MINIMUM IS
 REQUIRED AT THIS TIME.
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE:NO, PLEASE SEE THIS IS THE SAME NOTE, PLEASE
 SEE MISSING DISCONNECT AT THE CU.
 440.11, 110.26
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS ARE MISSING THE DISCONNECTS REQUIRED
 FOR THE A/C CU AND THE SPRINKLER PUMP/IRRIGATION.
 440.11, 430.31
  
 18) NOTE: OK.
  
 19) NOTE: OK.
  
 20) NOTE: OK.
  
 21) NOTE: OK.
  
 22) NOTE: OK.
  
 23) NOTE: OK.
  
  
 ** NEW NOTES **
  
 24) NOTE: PLEASE SEE RISER MENTIONS "RIGID" CONDUIT
 BEING INSTALLED, PLEASE VERIFY THIS AT THIS TIME, AS
 THIS TYPE OF CONDUIT FOR THIS INSTALLATION IS NOT
 USUAL. THIS DOES NOT VIOLATE ANY CODE, HOWEVER PLEASE
 KNOW IF INSTALLATION OF PVC CONDUIT IS USED INSTEAD
 WHICH IS OK, THEN AN EQUIPMENT GROUNDING CONDUCTOR
 WOULD BE REQUIRED TO CABANA AND PLANS WOULD BE REVISED
 TO INDICATE CONDUIT OTHER THAN "RIGID".
 THIS IS NOTED ONLY.
  
 25) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) GIVEN
 ONLY AS A NOTICE AT THIS TIME AS SOME COMMENTS WERE
 INDEED REPEAT COMMENTS FROM PREVIOUS REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-11-30 13:57:33FROM ZONING/INCOMING ON 11/29