2006-11-30 15:32:43 | ****** UNSAT2ND REVIEW ****** |
| |
| PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE |
| STILL IN NEED OF ADDRESSING, ALSO THERE ARE SOME NEW |
| NOTES BASED ON SOME CHANGES ON PLANS. |
| |
| 1) NOTE: OK |
| |
| 2) NOTE: NO, PLEASE STILL CLARIFY SERVICE EQUIPMENT. IS |
| THIS A 300A PANEL BOARD OF SOME KIND, A 300A METER MAIN |
| COMBO WITH TWO MAINS? |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CORRELATE PLANS AND RISER. RISER SHOWS WHAT |
| APPEARS TO BE A |
| 300A SERVICE, YET PLANS INDICATE 200A'S. |
| 230.70 , 215.5, 230.2 ETC |
| |
| 3) NOTE:NO, PLEASE SEE THE RISER DIAGRAM DOES NOT |
| INDICATE ANY SERVICE ENTRANCE CONDUCTORS? PLEASE SEE |
| THE CODE SECTIONS AS PREVIOUSLY NOTED WERE ADDED TO A |
| NOTE #19, HOWEVER IT IS NOT PERMITTED TO PLACE CODE |
| SECTIONS ON PLANS IN LIEU OF ACTUAL DETAIL OF DESIGN. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE RISER DOES NOT INDICATE ANY SEC'S . PLEASE |
| COMPLETE RISER. |
| 310.15B6,310.16,240.4 ETC |
| |
| 4) NOTE: OK. |
| |
| 5) NOTE:NO, SEE NOTE #2, FOR CLARIFICATION OF SERVICE |
| MAIN EQUIPMENT. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE PROVIDE INFORMATION FOR MAIN/PANEL/DISCONNECT ON |
| RISER WHICH FEEDS TWO SUB PANELS. PLEASE SEE 230.70 AS |
| THERE CAN BE NO MORE THAN 6 SPACES FOR EQUIPMENT AND NO |
| MORE THAN 6 MAINS FOR SERVICE. |
| |
| 6) NOTE: OK. |
| |
| 7) NOTE: OK. |
| |
| 8) NOTE: OK. |
| |
| 9) NOTE: OK. |
| |
| 10) NOTE: OK; HOWEVER SEE POSSIBLE NOTE UNDER 06081932 |
| AS THE SAME RISER SHOULD BE NOTED UNDER THAT REVIEW. |
| CABANA IS UNDER A SEPARATE PERMIT.. |
| |
| 11) NOTE: OK. |
| |
| 12) NOTE: OK. |
| |
| 13) NOTE: OK. |
| |
| 14) NOTE: NO, PLEASE SEE CIRCUITING WHICH HAS NOW BEEN |
| ADDED TO PLANS WHICH DO NOT CORRELATE WITH THE PANEL |
| SCHEDULE SUBMITTED. AS PREVIOUSLY NOTED, PLEASE ONLY |
| INDICATE THE AREAS WHICH ARE BEING FED FROM THE |
| CIRCUITS ON PANEL SCHEDULE. |
| PLEASE SEE NOW PLANS INDICATE BATH ROOM GFI"S BEING FED |
| FROM THE SMALL APPLIANCE CIRCUIT(S). |
| PLEASE SEE SMALL APPLIANCE CIRCUITS FEEDING BEDROOM, |
| HALLWAY, LIVING ROOM ETC. |
| PLEASE SEE ONLY ONE SMALL APPLIANCE CIRCUIT SHOWN IN |
| KITCHEN ETC. |
| PLEASE KNOW IT WAS ONLY REQUESTED TO INDICATE ON THE |
| PANEL SCHEDULE THESE AREAS/ROOMS. |
| PLEASE SEE THE FOLLOWING SECTIONS FOR ITEMS NOT |
| PERMITTED ON SMALL APPLIANCE OR BATHROOM CIRCUITS. |
| 210.52B1, 210.52D, 210.11C1, 210.11C3, 220.16 |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE COMPLETE PANEL SCHEDULE FOR ALL CIRCUITS TO THE |
| ROOMS AND AREAS IN WHICH THEY FEED. CIRCUITS ARE TO BE |
| SPECIFIC. IE: LIVING RM, KITCHEN LTS, ETC. |
| 408.6. |
| 106.1.2 |
| ** IT IS KNOWN TO THIS OFFICE THAT THE CIRCUITING WILL |
| BE REVISED AT A LATER DATE, HOWEVER THE MINIMUM IS |
| REQUIRED AT THIS TIME. |
| |
| 15) NOTE: OK. |
| |
| 16) NOTE: OK. |
| |
| 17) NOTE:NO, PLEASE SEE THIS IS THE SAME NOTE, PLEASE |
| SEE MISSING DISCONNECT AT THE CU. |
| 440.11, 110.26 |
| |
| **PREVIOUS REVIEW NOTE ** |
| PLEASE SEE PLANS ARE MISSING THE DISCONNECTS REQUIRED |
| FOR THE A/C CU AND THE SPRINKLER PUMP/IRRIGATION. |
| 440.11, 430.31 |
| |
| 18) NOTE: OK. |
| |
| 19) NOTE: OK. |
| |
| 20) NOTE: OK. |
| |
| 21) NOTE: OK. |
| |
| 22) NOTE: OK. |
| |
| 23) NOTE: OK. |
| |
| |
| ** NEW NOTES ** |
| |
| 24) NOTE: PLEASE SEE RISER MENTIONS "RIGID" CONDUIT |
| BEING INSTALLED, PLEASE VERIFY THIS AT THIS TIME, AS |
| THIS TYPE OF CONDUIT FOR THIS INSTALLATION IS NOT |
| USUAL. THIS DOES NOT VIOLATE ANY CODE, HOWEVER PLEASE |
| KNOW IF INSTALLATION OF PVC CONDUIT IS USED INSTEAD |
| WHICH IS OK, THEN AN EQUIPMENT GROUNDING CONDUCTOR |
| WOULD BE REQUIRED TO CABANA AND PLANS WOULD BE REVISED |
| TO INDICATE CONDUIT OTHER THAN "RIGID". |
| THIS IS NOTED ONLY. |
| |
| 25) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) GIVEN |
| ONLY AS A NOTICE AT THIS TIME AS SOME COMMENTS WERE |
| INDEED REPEAT COMMENTS FROM PREVIOUS REVIEW. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2006-11-30 13:57:33 | FROM ZONING/INCOMING ON 11/29 |