Notes
Date Text
2006-08-28 00:00:00DENIED;
 1.THE AUTOMATIC CLOTHES WASHER MUST
 DRAIN DOWN STREAM OF THE BATHROOM GROUP.
 FBC-2004 PLUMBING SECTION 909.1.
 2.THE AUTOMATIC CLOTHES WASHER BRANCH
 DRAIN IS REQUIRED TO BE 3" SECTION
 496.3.
 3.PLUMBING PLAN SHOWS A GAS WATER HEATER
 ELECTRICAL LOAD CALCULATION TABLE PAGE
 6/8 WATER HEATERIS LISTED AS ELECTRIC.
 PLEASE CHANGE ONE OF THE PAGES. IF WATER
 HEATER IS GAS THE A/C HANDLER WILL HAVE
 TO HAVE A DUCTED RETURN OR THE A/H
 CLOSET WILL HAVE TO BE AIR TIGHT.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695