2006-09-01 00:00:00 | *** DENIED *** |
| 1) ENERGY CALCULATIONS ARE CALLING FOR A |
| 5.6 KW HEATER, MECHANICAL PLANS ARE |
| CALLING FOR A 10 KW HEATER, THE TWO MUST |
| COINSIDE, PLEASE CORRECT. |
| |
| 2) CLOTHES DRYER VENT TERMINATION MUST |
| BE A MIN. OF 4 FT. FROM A/C CONDENSER |
| UNIT, PER 2004 FBC/M 501.2 .PLEASE |
| CORRECT. |
| |
| 3) ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA |
| SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. PER |
| FBC 104.2.1 . |
| |
| 4) PLEASE SIZE RETURN AIR GRILL TO AHU. |
| |
| 5) PLEASE PROVIDE RETURN AIR TO |
| BEDROOMS, SEE NOTE #6. |
| |
| 6) BALANCED RETURN AIR. |
| THIS MAY BE ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| INCREASING THE RETURN TRANSFER ONE AND |
| ONE HALF TIMES THE CROSS SECTIONAL AREA |
| (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING |
| AND THE DOOR HAVING AT LEAST AN |
| UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| PROPER RETURN AIR BALANCE. |
| (B)TRANSFER GRILLES SHALL USE 50 |
| SQUARE INCHES (OF GRILLE AREA) TO 100 |
| CFM (OF SUPPLY AIR) FOR SIZING |
| THROUGH-THE-WALL TRANSFER GRILLES AND |
| USING AN UNRESTRICTED 1-INCH |
| UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| RETURN AIR BALANCE |
| (C)HABITABLE ROOMS ONLY SHALL BE |
| REQUIRED TO MEET THESE REQUIREMENTS FOR |
| PROPER BALANCED RETURN AIR EXCLUDING |
| BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE |
| INCLUDED. PER 2004 FBC/R M1602.4 . |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |