Plan Review Notes
Plan Review Notes For Permit 06080554
Permit Number 06080554
Review Stop M
Sequence Number 1
Notes
Date Text
2006-09-01 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR A
 5.6 KW HEATER, MECHANICAL PLANS ARE
 CALLING FOR A 10 KW HEATER, THE TWO MUST
 COINSIDE, PLEASE CORRECT.
  
 2) CLOTHES DRYER VENT TERMINATION MUST
 BE A MIN. OF 4 FT. FROM A/C CONDENSER
 UNIT, PER 2004 FBC/M 501.2 .PLEASE
 CORRECT.
  
 3) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 4) PLEASE SIZE RETURN AIR GRILL TO AHU.
  
 5) PLEASE PROVIDE RETURN AIR TO
 BEDROOMS, SEE NOTE #6.
  
 6) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved