Plan Review Notes
Plan Review Notes For Permit 06080554
Permit Number 06080554
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-31 00:00:00****** UNSAT ******
  
 1) NOTE; PLEASE SUBMIT AIC RATINGS FOR
 ALL EQUIPMENT. NOTE MENTIONS 22K FOR
 MAIN DISCONNECT, HOWEVER INFORMATION ON
 RISER DOES NOT SHOW A MAIN DISCONNECT.
 PLEASE ALSO INCLUDE ALL OTHER SERVICE
 EQUIPMENT RATINGS.
 110.9
 FBC 106.1.2
  
 2) NOTE; PLEASE CORRELATE PLANS AND
 RISER. RISER SHOWS WHAT APPEARS TO BE A
 300A SERVICE, YET PLANS INDICATE 200A'S.
  
 230.70 , 215.5, 230.2 ETC
  
 3) NOTE: PLEASE SEE RISER DOES NOT
 INDICATEANY SEC'S . PLEASE COMPLETE
 RISER.
 310.15B6,310.16,240.4 ETC
  
 4) NOTE: PLEASE SEE RISER SHOWS 1/0'S
 FOR FEEDERS TO SUB PANEL, "A", YET THE
 MAIN BREAKER BEING SHOWN FEEDING THIS
 PANEL IS 200A'S. 1/0'S ARE NOT LARGE
 ENOUGH.
 310.16, 240.4
  
 5) NOTE: PLEASE PROVIDE INFORMATION FOR
 MAIN/PANEL/DISCONNECT ON RISER WHICH
 FEEDS TWO SUB PANELS. PLEASE SEE 230.70
 AS THERE CAN BE NO MORE THAN 6 SPACES
 FOR EQUIPMENT AND NO MORE THAN 6 MAINS
 FOR SERVICE.
  
 6) NOTE: PLEASE INDICATE THE SIZE OF THE
 METER CAN BEING PROVIDED.
 106.1.2 FBC
  
 7) NOTE: PLEASE CORRELATE RISER AND
 PANELS, AS PANEL FOR CABANA IS BEING
 SHOWN ONE SIZE AND RISER SHOWS ANOTHER.
 106.1.2 FBC
  
 8) NOTE: PLEASE SEE LOADS SHOWN FOR A/C
 INDICATES COMPRESSOR LOAD FOR THE 10KW,
 WHERE THE AHU, IS THE LARGER OF THE TWO,
 THE CALCULATIONS SHOULD INDICATE THE
 AHU.
 220.21., 220.31
  
 9) NOTE; PLEASE SEE MISSING GROUNDING
 ELECTRODE SYSTEM AT THE DETACHED
 BUILDING.
 250.32, 250.50.
  
 10) NOTE: ONCE RISER HAS BEEN CORRECTED
 FOR THE SIZE OF PANELS ETC AT CABANA,
 PLEASE BE SURE TO CLEARLY INDICATETHE
 MAIN DISCONNETC AT THE DEACHED BUILDING
 MEETING 225.31-225.39.
 PLEASE KNOW, SINCE PLANS FOR THE CABANA
 HAVE NOT BEEN SUBMITTED AT THIS TIME,
 THIS CAN NOT BE VERIFIED FOR CODE
 COMPLIANCE.
  
 11) NOTE: PLEASE SUBMIT AND COMPLETE
 PLANS FOR CABANA IF PART OF THIS PERMIT APPLICATION
 ETC. PLEASE KNOW, NO REVIEW
 COULD BE DONE FOR CABANA , AND THERE MAY
 BE COMMENTS TO FOLLOW.
 106.1.2 FBC, 2002 NEC.
  
 12) NOTE: PLEASE SEE 422.11(E)3,AS THE
 OCP FOR THE WATER HEATER CAN NOT EXCEED
 150%. PLEASE SEE 60A OCP IS BEING SHOWN
 ON A 5KW UNIT.
 PLEASE ADJUST.
 106.1.2
  
 13) NOTE: PLEASE SEE CONDUCTOR SIZE
 BEING SHOWN ON PANEL SCHEDULE FOR RANGE
 DOES NOT CLEARLY INDICATE THE SIZE.
 SEEMS TO CONTAIN A MISPRINT.
 310.16,240.4
  
 14) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 FOR ALL CIRCUITS TO THE ROOMS AND AREAS
 IN WHICH THEY FEED. CIRCUITS ARE TO BE
 SPECIFIC. IE: LIVING RM, KITCHEN LTS,
 ETC.
 408.6.
 106.1.2
 ** IT IS KNOWN TO THIE OFFICE THAT THE
 CIRCUITING WILL BE REVISED AT A LATER
 DATE, HOWEVER THE MINIMUM IS REQUIRED AT
 THIS TIME.
  
 15) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52 FOR 2' OF WALL SPACE OR MORE.
  
 16) NOTE: PLEASE SEE NOTE #7 ON PLANS
 WHICH REFERENCES A CODE IN THE NEC,
 PLEASE KNOW, HOWEVER THIS MUST BE FROM
 AN OLDER NEC, AS THE CURRENT NFPA-70 IN
 EFFECT DOES NOT CORRELATE WITH THIS
 ARTICALE BEING REFERENCED.
 PLEASE ADJUST.
  
 17) NOTE: PLEASE SEE PLANS ARE MISSING
 THE DISCONNECTS REQUIRED FOR THE A/C CU
 AND THE SPRINKLER PUMP/IRRIGATION.
 440.11, 430.31
  
 18) NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROL AT MASTER BEDRM TO
 AREAS WITH GRADE LEVEL ACCESS.
 210.70, LS 101 7.8
  
 19) NOTE: PLEASE KNOW, ALL FANS AND LT
 KITS WILL BE REQUIRED TO BE INSTALLED
 BEFORE FINALS, AS EGRESS LTS ARE
 REQUIRED. SINCE THE LIGHTING IS BEING
 SHOWN ON THE FANS, THESE WILL BE
 REQUIRED.
 ** PLEASE KNOW, IF USING A 1/2 SW RECEPT
 OR OTHER LIGHTING , THIS WOULD NOT BE
 REQUIRED.
 ** THIS NOTE IS FOR INFORMATIONAL
 PURPOSE ONLY.
  
 20) NOTE: PLEASE SEE RISER, PLEASE
 CLARIFY THE "9" BEING SHOWN AS THE
 DESRIPTION OF THE CONDUIT??
 IT IS UNCLEAR WHAT THIS IS?
 106.1.2
  
 21) NOTE: PLEASE SEE PLANS INDICATE
 SCOPE OF WORK BEING LOCATED IN "PALM
 BEACH COUNTY" , WHEN SCOPE OF WORK AND
 THIS JOB LOCATION IS LOCATED IN THE
 "CITY OF WEST PALM BEACH".
  
 22) NOTE: PLANS TO NOTE: SD'S TO BE
 INSTALLED PER NFPA-72 2002, 11.5.1.1,
 11.8.3
  
 23) NOTE: PLEASE SEE PLANS ARE MISSIGN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR SAID PLANS.
 FBC 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  