Date |
Text |
2006-09-05 00:00:00 | DENIED |
| |
| |
| 1.BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT SET OF |
| PLANS MUST BE STAMPED BY THAT OFFICE, |
| AND A COPY OF THE PAID RECEIPT ATTACHED |
| TO THE PERMIT APPLICATION. PLEASE CALL |
| (561)233-5025 FOR MORE INFORMATION. |
| |
| 2.BASED ON ICC BUILDING VALUATION DATA |
| THE PERMIT VALUE HAS BEEN REVISED TO |
| $213,721.ADDITIONAL PERMIT FEES ARE |
| DUE. |
| |
| 3.SUBMIT TWO SETS OF TRUSS DRAWINGS |
| FOR REVIEW PER 2004 FBC R-802.10.1 |
| TRUSS DRAWING REQUIRED TO BE APPROVED |
| PRIOR TO INSTALLATION. |
| |
| 4.R401.3 DRAINAGE. |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A |
| STORM SEWER CONVEYANCE OR OTHER APPROVED |
| POINT OF COLLECTION SO AS TO NOT CREATE |
| A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| DRAIN SURFACE WATER AWAY FROM FOUNDATION |
| WALLS. THE GRADE AWAY FROM FOUNDATION |
| WALLS SHALL FALL A MINIMUM OF 6 INCHES |
| WITHIN THE FIRST 10 FEET. |
| |
| 5.SELECT ROOF ASSEMBLY USED FOR THE |
| TAMKO ROOFING. |
| |
| 6.PRE-ENGINNERED TRUSSES, FBC 2309 IS |
| THE INCORRECT CODE SECTION USED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| OLD PAGES FOR REFERENCE . A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES |
| CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |