Plan Review Notes
Plan Review Notes For Permit 06080496
Permit Number 06080496
Review Stop B
Sequence Number 4
Notes
Date Text
2007-04-10 16:54:00BUILDING REVISION SECOND CHECKLIST:
 1- THERE ARE NO REVISED PLANS SHOWING LOCATION OF NEW
 SINGLE HUNG WINDOWS. PROVIDE REVISED PLANS.
  
 2- STORM SHUTTERS DRAWINGS ARE INCOMPLETE. ONLY SHEET 1
 OF 19 WAS SUBMITTED.
  
 3- ARCHITECT'S REVIEW STAMP DOESN'T STATE IF PRODUCT
 APPROVAL WAS APPROVED OR NOT.REVIEW STAMP IS BLANK.
 NOTHING IS MARKED STATINGWHAT ACTION WAS TAKENWITH
 HIS REVIEW.
  
 4- ON PREVIOUS CHECKLIST IT WAS REQUESTED TO PROVIDE
 COMPLETE INFORMATION SHOWING HOW STORM PANELS ARE GOING
 TO BE INSTALLED.THIS INFORMATION WAS NOT PROVIDED.
 INDICATE IN DRAWINGS SPECIFIC ANCHOR TYPE AND SPACING
 TO BE USED TO VERIFY COMPLIANCE WITH PROPOSED
 INSTALLATION. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 5- FLORIDA PRODUCT APPROVAL FL1435 HAS NOTHING TO DO
 WITH NOA 06-0706.04. PROVIDE EITHERDADE COUNTY NOA
 ALONE OR COMPLETE INFORMATION THAT WAS PROVIDED TO
 OBTAIN FL1435 APPROVAL.ARCHITECT TO REVIEW AND
 APPROVE SUCH PRODUCT APPROVAL AND USEORIGINAL STAMP
 AS USED WITH PRODUCT APPROVAL FOR STORM SHUTTERS. COPY
 OF REVIEW STAMP IS NOT ACCEPTABLE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712