Plan Review Notes
Plan Review Notes For Permit 06080468
Permit Number 06080468
Review Stop B
Sequence Number 3
Notes
Date Text
2007-01-23 16:30:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 1.)PLEASE SEE PREVIOUS LISTS IN REGARDS TO USING WALL
 PRESSURES FOR THE SOFFIT.ALSO NOTE, FROM EMAIL FROM
 ROBERT BROWN ABO TO JASON HANCHUK, PE, THE FOLLOWING:
  
 I HAVE REVIEWED THE EXAMPLE THAT YOU SENT.AS
 PREVIOUSLY STATED, I AGREE THAT ONE LOAD CASE IS 'WIND
 PERPENDICULAR TO WALL' AND THAT YOUR METHODOLOGY
 ADDRESSES THAT LOADCASE.THE WIND LOAD ON THE SOFFIT
 UNDER THAT LOAD CASE IS A POSITIVE PRESSURE.
  
 HOWEVER, WHEN WE SPOKE YESTERDAY AND AGAIN TODAY, AND
 WHEN I SPOKE TO MR KELAHER, I POINTED OUT THAT THERE IS
 A CASE AT THE EAST-WEST GRADE LEVEL WALKWAY FROM OLIVE
 AVENUE TO DIXIE HWY WHERE THERE IS NO WALL (SEE SHEET
 A-1 OF LOUIS C. KALLINOSIS, AIA PLANS).AS I STATED,
 IN THAT LOCATION, THE WIND WILL ACCELERATE ACROSS THAT
 SOFFIT IN THE SAME MANNER THAT IT DOES ACROSS A FLAT
 ROOF.THAT ACCELERATION WILL RESULT IN NEGATIVE
 PRESSURES (SUCTION) ON THE SOFFIT IN EXCESS OF THE
 PROPOSED ZONE 4 WALL PRESSURE STATED IN THE WIND DESIGN
 LOAD CALCULATIONS.I DO NOT SEE THATYOU OR MR
 KELAHER HAVE ADDRESSED THAT LOAD CASE.
  
 I DISAGREE WITH THE SECOND PARAGRAPH OF YOUR LETTER
 DATED 1/8/06 (SHOULD BE 2007?) ADDRESSED TO ALLEN
 PADILLA.IT STATES THAT ZONE 2 AND 3 LOADS ARE
 OVERHANG LOADS.I WOULD CONTEND THAT FOR A FLAT ROOF
 THERE IS NO OVERHANG.IF YOU REFER TO FIGURE 6-3 IN
 ASCE7-02 YOU WILL SEE THAT FOR A FLAT ROOF THERE IS NO
 OVERHANG FOR ZONE 2 AND 3.ALSO FIGURE 6-11B IN
 ASCE7-02 WHICH GIVES EXTERNAL PRESSURE COEFFICIENTS FOR
 GABLE ROOFS WITH SLOPE RANGING FROM 0O (I.E. FLAT) TO
 7O, GIVES PRESSURE COEFFICIENTS FOR ZONE 2 AND 3 ON THE
 ROOF AND THEN GIVES SEPARATE COEFFICIENTS FOR ZONE 2
 AND 3 AT THE OVERHANGS.THIS WOULD NOT BE THE CASE IF
 ZONE 2 AND 3 WERE FOR OVERHANGS ONLY.
  
 WE ALSO NEED TO CONSIDER THE CASE OF 'WIND PARALLEL TO
 THE WALL'.THIS LOADCASE WILL RESULT IN A NEGATIVE
 PRESSURES (SUCTION) ON THE SOFFIT IN EXCESS OF THE
 PROPOSED ZONE 4 WALL PRESSURE STATED IN THE WIND DESIGN
 LOAD CALCULATIONS.
  
 I DO NOT FOR ONE MOMENT CONSIDER DESIGN FOR WIND LOAD
 TO BE AN EXACT SCIENCE BUT I BELIEVE THE PROPOSED
 DESIGN TO BE NON-CONSERVATIVE AS THE WORST CASE
 NEGATIVE PRESSURE LOADCASE DOES NOT APPEAR TO HAVE BEEN
 FULLY INVESTIGATED.THE FACT THAT THESE REPAIRS ARE
 EVEN NECESSARY WOULD IMPLY THAT THE SOFFIT ON THIS
 BUILDING WAS SUBJECTED TO SIGNIFICANT NEGATIVE WIND
 PRESSURE EVEN DURING THE 'LESS-THAN-DESIGN' WIND
 EVENT(S) THAT CAUSED THE FAILURE.EITHER PROVIDE
 JUSTIFICATION FOR THE USE OF ZONE 4 WALL PRESSURES FOR
 THE CASE AT THE SOFFIT ABOVE THE EAST-WEST WALKWAY AND
 FOR THE 'WIND PARALLEL TO THE WALL' CASE, OR AMEND THE
 NEGATIVE PRESSURES IN THE WIND DESIGN LOAD
 CALCULATIONS.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved