Plan Review Notes
Plan Review Notes For Permit 06080468
Permit Number 06080468
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-09-15 00:00:00*****UNSAT*****
  
  
  
  
 1.) STRUCTURES UNDERGOING CONSTRUCTION,
 ALTERATION, OR DEMOLITION OPERATIONS
 SHALL COMPLY WITH NFPA 241.
  
 2.) ACCUMULATIONS OF COMBUSTIBLE WASTE
 MATERIAL AND DUST DEBRIS SHALL BE
 REMOVED FROM THE STRUCTURE AND ITS
 IMMEDIATE VICINITY AT THE END OF EACH
 SHIFT OR MORE FREQUENTLY AS NECESSARY
 FOR SAFE OPERATIONS.
  
 3.) ALL EXIT COMPONENTS SHALL BE
 MAINTAINED, CLEAR AND UNOBSTRUCTED.
  
 4.) CONSTRUCTION AND/OR DEMOLITION
 OPERATIONS SHALL NOT INTERFERE OR HINDER
 EMERGENCY ACCESS TO THE SAID PROPERTY
 (INCLUDING FIRE LANES).
  
 5.) NFPA 101, 2003 EDITION AND FLORIDA
 FIRE PREVENTION CODE, 2004 EDITION SHALL
 BE REFERENCED.
  
 6.) INDICATE ON THE PLANS THE LOCATION
 OF FIRE PROTECTION SYSTEMS (I.E.
 SPRINKLER HEADS, SMOKE DETECTORS, ETC.)
 AND WHETHER THE LISTED SCOPE OF WORK
 WILL AFFECT THEIR OPERATION.
  
 7.) IF THE FIRE ALARM AND/OR SPRINKLER
 SYSTEM IS/ARE MODIFIED DUE TO THE SCOPE
 OF WORK, SEPARATE SHOP PLANS/DRAWINGS
 AND PERMIT WILL BE REQUIRED.
  
  
  
 **PLEASE SUBMIT OR ADDRESS THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE DO NOT HESITATE TO
 CALL.**
  
  