2006-08-23 00:00:00 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE PLANS STATE "WORK TO |
| COMPLY WITH APPLICABLE CODES". PLEASE |
| KNOW, PLANS SHALL STATE THE CODES AND |
| DESIGN SPECIFIC IN DESIGN. |
| PLANS SHOULD REFLECT CODES FOR RELEVANT |
| WORK IN SCOPE. |
| FBC 2004, NFPA-70 2002 . (NEC). |
| |
| 2) NOTE: PLEASE SEE OTHER NOTE ON PLANS |
| MENTIONS CIRCUITING WAS VERIFIED IN |
| ORDER TO ADDED NEW FIXTURES WITH THE |
| INCREASED WATTAGE, HOWEVER BASED ON THE |
| NUMBE ROF FIXTURES SHOWN ON SOME |
| CIRCUITS AND THE VOLTAGE OF SAID |
| CIRCUITS NOT BEING SHOWN, PLEASE SEE |
| CIRCUIT(S) WHICH APPEAR TO BE OVER |
| LOADED. |
| PLEASE SEE VOLTAGE SHOULD BE STATED FOR |
| EEACH OF THE PANELS/SYSTEMS FOR EXISTING |
| CIRCUITS. 120, 208, 277 ETC. |
| PLEASE ALSO KNOW, ALL CONTINUOUS LOADS |
| SHOULD BE VERIFIED FOR NEW LOADS. |
| (3 OR MORE HRS). |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |