Plan Review Notes
Plan Review Notes For Permit 06080468
Permit Number 06080468
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-23 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS STATE "WORK TO
 COMPLY WITH APPLICABLE CODES". PLEASE
 KNOW, PLANS SHALL STATE THE CODES AND
 DESIGN SPECIFIC IN DESIGN.
 PLANS SHOULD REFLECT CODES FOR RELEVANT
 WORK IN SCOPE.
 FBC 2004, NFPA-70 2002 . (NEC).
  
 2) NOTE: PLEASE SEE OTHER NOTE ON PLANS
 MENTIONS CIRCUITING WAS VERIFIED IN
 ORDER TO ADDED NEW FIXTURES WITH THE
 INCREASED WATTAGE, HOWEVER BASED ON THE
 NUMBE ROF FIXTURES SHOWN ON SOME
 CIRCUITS AND THE VOLTAGE OF SAID
 CIRCUITS NOT BEING SHOWN, PLEASE SEE
 CIRCUIT(S) WHICH APPEAR TO BE OVER
 LOADED.
 PLEASE SEE VOLTAGE SHOULD BE STATED FOR
 EEACH OF THE PANELS/SYSTEMS FOR EXISTING
 CIRCUITS. 120, 208, 277 ETC.
 PLEASE ALSO KNOW, ALL CONTINUOUS LOADS
 SHOULD BE VERIFIED FOR NEW LOADS.
 (3 OR MORE HRS).
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  