Plan Review Notes For Permit 06080462 |
Permit Number |
06080462 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-09-26 00:00:00 | *****APPROVED***** W/REMINDERS | | | | | | | | | | 1.) PLEASE BE ADVISED THAT NFPA 72, 2002 | | EDITION, SHALL BE REFERENCED. | | | | 2.) DUCT SMOKE DETECTORS SHALL INITIATE | | A GENERAL ALARM. | | | | 3.) FIRE ALARM SYSTEM IN CONJUNCTION | | WITH THE FIRE SPRINKLER SYSTEM TO BE | | MONITORED. | | | | 4.) WATERFLOW TO ACTIVATE A GENERAL | | WITHIN 45 TO 60 SECONDS. | | | | 5.) FIRE ALARM SYSTEM SHALL BE UL | | CERTIFIED FOR CENTRAL STATION. INSTALL | | AND/OR POST UL CERTIFICATE AT THE FIRE | | ALARM CONTROL PANEL AND PROVIDE A COPY | | TO WPBFR BY THE FINAL FIRE ALARM | | INSPECTION. | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|