Plan Review Notes
Plan Review Notes For Permit 06080462
Permit Number 06080462
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-09-26 00:00:00*****APPROVED***** W/REMINDERS
  
  
  
  
 1.) PLEASE BE ADVISED THAT NFPA 72, 2002
 EDITION, SHALL BE REFERENCED.
  
 2.) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL ALARM.
  
 3.) FIRE ALARM SYSTEM IN CONJUNCTION
 WITH THE FIRE SPRINKLER SYSTEM TO BE
 MONITORED.
  
 4.) WATERFLOW TO ACTIVATE A GENERAL
 WITHIN 45 TO 60 SECONDS.
  
 5.) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFIED FOR CENTRAL STATION. INSTALL
 AND/OR POST UL CERTIFICATE AT THE FIRE
 ALARM CONTROL PANEL AND PROVIDE A COPY
 TO WPBFR BY THE FINAL FIRE ALARM
 INSPECTION.
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722