Plan Review Notes
Plan Review Notes For Permit 06080439
Permit Number 06080439
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FBC-2004 BUILDING
  
 1. BUILDING SHALL BE DESIGNED TO THE
 FBC-2004 CODE. PLEASE INDICATE ON PLANS.
 SECTION 106.1.1
  
 2. PROVIDE AN EXISTING FLOOR PLAN TO
 DETERMINE EXTENT OF ALTERATION. SECTION
 106.1.1.
  
 3. SHT A1.2 IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5.
  
 4. SHT A2.1 A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1. NO DRAINAGE OR
 WATER SUPPLY IS SHOWN TO THE DRINKING
 FOUNTAIN. PLEASE CLARIFY.
  
 5. SHT A2.1 ACCESSIBILITY REQUIREMENTS.
 SHOW THE FOLLOWING:
 FOR W/C'S
 A. 11-4.16.5 FLUSH CONTROLS
 FOR LAV'S
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
  
 6. SHT A2.1 SHOWS A FREE STANDING
 DRINKING FOUNTAIN, AND A WALL HUNG
 DRINKING FOUNTAIN DETAIL. PLEASE
 INDICATE WHICH TYPE WILL BE INSTALLED.
 SECTION 106.1.1. IF THE WALL HUNG TYPE
 WILL BE USED, A FORWARD APPROACH CLEAR
 FLOOR SPACE IS REQUIRED. SECTION
 11-4.15.5. ALSO SHOW PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING AS REQUIRED BY SECTION
 11-4.1.3(10)(A), IF THIS IS NOT A
 HIGH/LOW DRINKING FOUNTAIN.
  
 7. SHT A4.1 SCUPPERS SHOWN ON SHT A5.1
 ARE NOT SHOWN ON THE ELEVATIONS. PLEASE
 INDICATE THE SCUPPERS. SECTION 106.1.1.
  
 8. SHT A5.1 SUBMIT CALCULATIONS FOR THE
 ROOF DRAINS PER SECTIONS 1106 & 1107
 WITH ALL SUBSECTIONS. SIZE GUTTERS AND
 DOWNSPOUTS REQUIRED BY SECTION 1503.6
 PER TABLES 1106.3 AND 1106.6. SHOW THE
 SQUARE FOOTAGE BEING DRAINED BY EACH
 DOWNSPOUT. SHOW ENTIRE SQUARE FOOTAGE
 BEING DRAINED AS WELL AS 1/2 AREA OF ALL
 VERTICAL WALLS, INCLUDING PARAPETS, IN
 THE CALCULATIONS. INDICATE SLOPE OF THE
 GUTTER AND INDICATE THE LOCATION OF THE
 HIGH SPOTS OF THE GUTTER.
  
 9. SHT A5.1 SEPARATE PRIMARY AND
 SECONDARY ROOF DRAINS ARE REQUIRED ON
 THE LOWER ROOF. SUBMIT CALCULATIONS
 SHOWING THE SQUARE FOOTAGE OF THE ROOF
 AS WELL AS 1/2 AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS. SHOW THE
 PRIMARY ROOF DRAINS. DETAIL SHOWN
 INDICATES EMERGENCY OVERFLOW SCUPPERS AS
 THE FLOW LEVEL IS 2" TO $' OFF THE ROOF.
  
 10. SUBMIT A WATER RISER DIAGRAM. SHOW
 ALL PIPE SIZES, VALVES, WATER HAMMER
 ARRESTORS, (IF REQUIRED BY SECTION 604.9
 - (W/M'S, D/W'S, OR ICE MAKERS). ALSO
 SEE SECTION 606.1(4). SECTION
 106.3.5.1.3.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]