2006-09-05 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FBC-2004 BUILDING |
| |
| 1. BUILDING SHALL BE DESIGNED TO THE |
| FBC-2004 CODE. PLEASE INDICATE ON PLANS. |
| SECTION 106.1.1 |
| |
| 2. PROVIDE AN EXISTING FLOOR PLAN TO |
| DETERMINE EXTENT OF ALTERATION. SECTION |
| 106.1.1. |
| |
| 3. SHT A1.2 IN THE INSTALLATION OR |
| REMOVAL OF ANY PART OF A DRAINAGE |
| SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| SECTION 704.5. |
| |
| 4. SHT A2.1 A DRINKING FOUNTAIN IS |
| REQUIRED PER TABLE 403.1. NO DRAINAGE OR |
| WATER SUPPLY IS SHOWN TO THE DRINKING |
| FOUNTAIN. PLEASE CLARIFY. |
| |
| 5. SHT A2.1 ACCESSIBILITY REQUIREMENTS. |
| SHOW THE FOLLOWING: |
| FOR W/C'S |
| A. 11-4.16.5 FLUSH CONTROLS |
| FOR LAV'S |
| A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| B. 11-4.19.5 FAUCETS |
| |
| 6. SHT A2.1 SHOWS A FREE STANDING |
| DRINKING FOUNTAIN, AND A WALL HUNG |
| DRINKING FOUNTAIN DETAIL. PLEASE |
| INDICATE WHICH TYPE WILL BE INSTALLED. |
| SECTION 106.1.1. IF THE WALL HUNG TYPE |
| WILL BE USED, A FORWARD APPROACH CLEAR |
| FLOOR SPACE IS REQUIRED. SECTION |
| 11-4.15.5. ALSO SHOW PROVISIONS FOR |
| THOSE WHO HAVE DIFFICULTY BENDING OR |
| STOOPING AS REQUIRED BY SECTION |
| 11-4.1.3(10)(A), IF THIS IS NOT A |
| HIGH/LOW DRINKING FOUNTAIN. |
| |
| 7. SHT A4.1 SCUPPERS SHOWN ON SHT A5.1 |
| ARE NOT SHOWN ON THE ELEVATIONS. PLEASE |
| INDICATE THE SCUPPERS. SECTION 106.1.1. |
| |
| 8. SHT A5.1 SUBMIT CALCULATIONS FOR THE |
| ROOF DRAINS PER SECTIONS 1106 & 1107 |
| WITH ALL SUBSECTIONS. SIZE GUTTERS AND |
| DOWNSPOUTS REQUIRED BY SECTION 1503.6 |
| PER TABLES 1106.3 AND 1106.6. SHOW THE |
| SQUARE FOOTAGE BEING DRAINED BY EACH |
| DOWNSPOUT. SHOW ENTIRE SQUARE FOOTAGE |
| BEING DRAINED AS WELL AS 1/2 AREA OF ALL |
| VERTICAL WALLS, INCLUDING PARAPETS, IN |
| THE CALCULATIONS. INDICATE SLOPE OF THE |
| GUTTER AND INDICATE THE LOCATION OF THE |
| HIGH SPOTS OF THE GUTTER. |
| |
| 9. SHT A5.1 SEPARATE PRIMARY AND |
| SECONDARY ROOF DRAINS ARE REQUIRED ON |
| THE LOWER ROOF. SUBMIT CALCULATIONS |
| SHOWING THE SQUARE FOOTAGE OF THE ROOF |
| AS WELL AS 1/2 AREA OF ALL VERTICAL |
| WALLS INCLUDING PARAPETS. SHOW THE |
| PRIMARY ROOF DRAINS. DETAIL SHOWN |
| INDICATES EMERGENCY OVERFLOW SCUPPERS AS |
| THE FLOW LEVEL IS 2" TO $' OFF THE ROOF. |
| |
| 10. SUBMIT A WATER RISER DIAGRAM. SHOW |
| ALL PIPE SIZES, VALVES, WATER HAMMER |
| ARRESTORS, (IF REQUIRED BY SECTION 604.9 |
| - (W/M'S, D/W'S, OR ICE MAKERS). ALSO |
| SEE SECTION 606.1(4). SECTION |
| 106.3.5.1.3. |
| |