Plan Review Notes
Plan Review Notes For Permit 06080439
Permit Number 06080439
Review Stop M
Sequence Number 1
Notes
Date Text
2006-09-20 00:00:00*** DENIED ***
 1) SEE ENERGY CAL'S. PAGE 6 AND
 COMPLETE.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2
  
 3) PLEASE PROVIDE OUTDOOR AIR AND
 OUTDOOR AIR CALCULATIONS, PER 2004 FBC/M
 403.2 .
  
 4) PLEASE SHOW SIZES OF SUPPLY AIR DUCTS
 (FLEX) TO NEW ADDITION AND TO BATHROOMS
 IN EXISTING.
  
 5) PLEASE SEE HIGH LITED WALLS ON
 MECHANICAL PLAN AS THEY ARE FIRE RATED
 AND REQUIRE FIRE DAMPERS.
  
 6) PLEASE SHOW A MANUFACTURE DETAIL FOR
 FIRE DAMPERS ON PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.