2006-08-27 00:00:00 | ***** UNSAT ***** |
| |
| 1) NOTE: PLEASE SEE THE SOIL BEARING |
| REPORTS , FIELD REPORTS ARE IN FACT |
| SEALED WITH A RAISED SEAL OVER |
| SIGNATURES WHICH ARE PHOTO-COPIES OF |
| ORIGINAL SIGNATURES. PLEASE SEE FLORIDA |
| ADMINISTRATIVE CODE 61G15-23.002 AND |
| FLORIDA STATUES 471.025, AS BOTHE OF |
| THESE REQUIRE ALL SIGNATURES TO BE |
| ORIGINAL. |
| THIS IS REQUIRED WHETHER OR NOT COMMENT |
| IS MADE BY OTHER REVIEWER(S). |
| |
| 2) NOTE: PLEASE SEE NOC WAS RECORDED ON |
| 6/21/06 WHICH WAS RECORDED WITHOUT THE |
| PCN/TAX FOLIO NUMBER ON SAID DOCUMNET. |
| PLEASE ALSO KNOW FOR INFORMATION |
| PRUPOSES, THE NOC WILL BECOME VOID IF |
| WORK HAS NOT COMMENCED WITHIN 90 DAYS OF |
| RECORDING SUCH NOC. PLEASE KNOW THE NOC |
| IS ONLY REQUIRED BEFORE PICKING UP |
| PERMIT. |
| FS 713.13(2). |
| |
| 3) NOTE: PLEASE SEE ONLY ONE COPY OF THE |
| FLORIDA ENERGY CODE CALCULATIONS WAS |
| SUBMITTED. |
| 2004 FBC CHAPTER 13 |
| |
| 4) NOTE: PLEASE INDICATE AND SHOW ALL |
| ROOM AND AREA DESIGNATIONS ON PLANS. |
| PLEASE COMPLETE ALL CIRCUITING ON PLANS |
| AND PLEASE CORRELATE ALL CIRCUTING ON |
| PLANS WITH THE PANEL SCHEDULE(S) |
| SUBMITTED. PLEASE KNOW, CIRCUITS SHALL |
| BE SPECIFIC TO AREAS/ROOMS ARE SHOWN ON |
| PLANS. *GEN LTS AND GEN RECEPTS NEEDS TO |
| BE MORE SPECIFIC* |
| 408.4, 310.16, 240.4 |
| |
| 5) NOTE: PLEASE BE SURE PLANS REFLECT |
| ALL THE CURRENT RELEVANT CODES SURRENTLY |
| ADOPTED BY THE STATE OF FLORIDA. |
| PLEASE SEE PLANS DO SHOW THE 2001 FBC IN |
| SOME LOCATIONS. |
| PLEASE SEE WE ARE CURRENTLY UNDER THE |
| 2002 NFPA-70(NEC), 2002 NFPA-72, 2003 |
| NFPA-101, 2004 FBC. |
| 106.1 |
| |
| 6) NOTE: PLEASE CLARIFY RISER AS SHOWN. |
| PLEASE SEE AN ADDITIONAL METER CAN IS |
| BEING SHOWN FOR WHAT WOULD BE A NEW |
| TENANT, HOWEVER THIS IS ONLY ONE TENANT |
| AND ONLY ONE METER WIL BE PERMITTED |
| UNLESS PROPER TENANT SEPARATION IS |
| BUILT. |
| PLEASE ALSO SEE RISER SHOWS A NEW MAIN |
| DISCONNECT ON THE LINE SIDE OF THE FPL |
| METERS. PLEASE SEE FPL SERVICE STANDARDS |
| AS THE MAINS WOULD BE REQUIRD ON THE |
| LOAD SIDE. |
| PLEASE SEE RISER AS SHOWN MUST BE |
| RE-DESIGNED. |
| 90.4. |
| FBC 106.1.2 |
| |
| 7) NOTE: PLEASE SEE MISSING GROUNDFING |
| ELECTRODE SYSTEM PER 250.50. |
| PLEASE COMPELTE, NEW FOOTER STEEL, COLD |
| WATER PIPES ETC. |
| |
| 8) NOTE: PLEASE SEE LTS IN MANY |
| LOCATIONS ARE BEING SHOWN AS A "J" WHERE |
| IT APPEARS TO BE A 2X4 LAYIN TYOE |
| FIXTURE. PLEASE CLARIFY IF THE "J" IS |
| THE FIXTURE TYPE, THEN PLEASE INCLUDE |
| ON THE FIXTURE SCHEDULE. PLEASE KNOW, |
| LTS ARE REQUIRED IN ALL THESE LOCATIONS |
| FOR MEANS OF EGREES ETC. |
| NFPA-101 7.8 |
| |
| 9) NOTE: PLEASE SEE NOTE ABOVE #8, AS |
| THE SAME IS SHOWN IN AHU CLOSETS. |
| PLEASE SEE 210.70 |
| PLEASE ALSO SEE MISSING RECEPTS FOR |
| AHU'S, AND MISSING GFI FOR CU'S . |
| 210.63, 210.87 |
| |
| 10) NOTE: PLEASE SEE MISSING DISCONNECTS |
| FOR AHU'S , 440.11,110.26 |
| |
| 11) NOTE: PLEASE SEE MISSING SIGN |
| CIRCUIT(S). 600.5, 220.3(B)(6) |
| |
| 10) NOTE: PLEASE SUBMIT AND SHOW |
| COMPLETE LOAD CALCULATTIONS FOR |
| COMMERCIAL BUILDINGS. 220.3,220.10, |
| 220.11,220.13, ETC AND ALL CONTINUOUS |
| LOADS PER 215.3, 230.42 ETC |
| |
| 11) NOTE: PLEASE SEE LAODS ON PANELS ARE |
| SHOWING BOTH THE COND UNITS AND THE |
| AHU'S. PLEASE SEE 220.11 |
| |
| ** PLEASE BE AWARE OF ANY COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |