2006-09-05 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06080439 |
| ADD: 2825 AUSTRALIAN AV |
| CONT: TURSO CONTRACTING CO |
| TEL: (561)358-4246 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| INFORMATION THAT IS REQUIRED FOR RECORD |
| KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED.2004 EXISTING |
| BUILDING CODE INDICATE THE LEVEL OF |
| ALTERATIONS? |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| IS REQUIRED. |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| OF THE BUILDING PERMIT. |
| G) OCCUPANT LOAD |
| H) FLOOD ZONE |
| I) FLOOD ELEVATION |
| |
| 3) SHEET A1.2 NOTE# 9 INDICATES GLAZING |
| TO MEET THE REQUIREMENTS OF FBC 2001 |
| PLEASE CORRECT TO THE CURRENT CODE FBC |
| 2004. |
| |
| 4) SHEET A1.1 PLEASE PROVIDE ELEVATIONS |
| FOR THE SITE PLAN.11-4.3.7 SLOPE. |
| AN ACCESSIBLE ROUTE WITH A RUNNING SLOPE |
| GREATER THAN 1:20 IS A RAMP AND SHALL |
| COMPLY WITH SECTION 11-4.8 . NOWHERE |
| SHALL THE CROSS SLOPE OF AN ACCESSIBLE |
| ROUTE EXCEED 1:50. |
| |
| 5) 2004 FL. BLD CODE 1603.1.4 THE |
| FOLLOWING INFORMATION RELATED TO WIND |
| SHALL BE SHOWN ON THE CONSTRUCTION |
| DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| |
| 6) SHEET A8.1 INDICATES 2 SECTIONS |
| 1-2/S1 THERE ARE NO STRUCTURAL SHEETS, |
| ONLY "A" SHEETS. |
| |
| 7) SHEET A8.2 SAME ISSUE PLAN DETAILS |
| INDICATE STRUCTURAL SHEETS. |
| |
| 8) A8.3 DETAILS OF STEEL COLUMN AND |
| 8"X30" STEEL EMBED PLATE DOESN'T |
| INDICATE THE TYPE OF WELDNOR SIZE OF |
| WELD. 106.1.2* ADDITIONAL INFO REQUIRED. |
| |
| 9) SHEET A8.3 DETAIL# 2&4 INDICATES A |
| STEEL PARAPET BUT NO ATTACHMENT METHOD |
| IS PROVIDED?106.1.2* ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 10) A8.3 STEEL STUD PARAPET DETAILS ARE |
| MISSING DETAILS SUCH AS : |
| 10A) WEATHER RESISTANT BARRIER 2510.6 |
| 10B) TYPE OF WIRE LATH, WEIGHT OF WIRE |
| LATH, AND ATTACHMENT, ASTM C1063. |
| |
| 11) WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 12) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 13) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| 1) TAMKO BUR ROOF SYSTEMS |
| ONLY THE FIRST 4 SHEETS OF THIS REPORT |
| WERE SUBMITTED. NO SUBSYSTEM WAS |
| SUBMITTED OR HIGHLIGHTED. NOTE SYSTEMS |
| LIMITATION# 7. FOR THIS PROJECT THERE |
| WILL NEED TO HAVE 3 SEPERATE SUBSYSTEMS |
| ONE FOR CONCRETE TWIN TEES WITH |
| INSULATED DECK, ONE FOR SSTEEL DECK WITH |
| INSULATION AND A STEEL DECK NO |
| INSULATION. |
| THIS ROOF IS MISSING OR NOT IN |
| COMPLIANCE WITH THE FOLLOW ITEMS: |
| |
| _X__ CONTRACTOR DID NOT PROVIDE THE MEAN |
| |
| ROOF HEIGHT. |
| |
| ___ CONTRACTOR DID NOT INDICATE THE ROOF |
| PITCH. |
| |
| _X__ CONTRACTOR FAILED TO INDICATE WHICH |
| SYSTEM TO BE USED. |
| |
| _X__ THE SYSTEM PROVIDED HAS A LOW |
| PRESSURE FOR ZONE _3__ . |
| |
| __X_ THE SYSTEM PROVIDED STATES |
| LIMITATION# 7, SHOULD THE FASTENER |
| RESISTANCE BE LESS THAN THAT |
| REQUIRED, AS DETERMINED BY THE |
| BUILDING OFFICIAL, A REVISED |
| FASTENER SPACING, PREPARED , SIGNED |
| AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOF |
| CONSULTANT MAY BE SUBMITTED. |
| |
| ___THE SYSTEM PROVIDED INDICATES |
| LIMITATION# 9, NO ENHANCED |
| FASTENING ALLOWED. |
| |
| 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| BUILDING PROVISO: |
| 109.3.10* IMPACT OF CONSTRUCTION. ALL |
| CONSTRUCTION ACTIVITY REGULATED BY THIS |
| CODE SHALL BE PERMORMED IN A MANNER SO |
| AS NOT TO ADVERSELY IMPACT THE CONDITION |
| OF ADJACENT PROPERTY, UNLESS SUCH |
| ACTIVITY IS PERMITTED TO AFFECT SAID |
| PROPERTY PURSUANT TO A CONSENT BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| CONDITIONS AGREEABLE TO THE APPLICABLE |
| PROPERTY OWNER.THIS INCLUDES BUT IS NOT |
| LIMITED TO THE CONTROL OF DUST, NOISE, |
| WATER OR DRAINAGE RUN-OFF, DEBRIS, AND |
| THE STORAGE OF CONSTRUCTION MATERIALS. |
| NEW CONSTRUCTION ACTIVITY SHALL NOT |
| ADVERSELY IMPACT HISTORIC SURFACE WATER |
| DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, & MAY REQUIRE SPECIAL |
| DRAINAGE DESIGN COMPLYING WITH |
| ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE PATTERNS OF THE AFFECTED SITES. |
| ACCORDINGLY, DEVELOPERS, CONTRACTORS, |
| AND OWNERS OF ALL NEW RESIDENTIAL |
| DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| PATIOS, DRIVEWAYS, DECKS, OR SIMILAR |
| ITEMS, ON EXISTING PROPERTIES RESULTING |
| IN A DECREASE IN EXCESS OF 800SQ FT OF |
| PERMEABLE LAND AREA ON ANY PARCELL SHALL |
| AS A PERMIT CONDITION, PROVIDE A |
| PROFESSIONALLY PREPARED DRAINAGE PLAN |
| CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE |
| IMPROVEMENT, A CERTIFICATE FROM A |
| LICENSED ENGINEER SHALL BE SUBMITTED TO |
| THE INSPECTOR IN ORDER TO RECEIVE |
| APPROVAL OF THE FINAL INSPECTION. |
| |
| 109.3.10.1 HURICANE PROTECTION. |
| IT SHALL BE UNLAWFUL FOR ANY PERSON TO |
| ALLOW CONSTRUCTION RELATED MATERIALS |
| EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| OTHERWISE UNSECURED AT A CONSTRUCTION |
| SITE FROM 24 HRS. AFTER A HURRICANE |
| WATCH HAS BEEN ISSUED UNTIL THE |
| HURRICANE WATCH OR WARNING HAS BEEN |
| LIFTED. ALL SUCH CONSTRUCTION MATERIALS, |
| EQUIPMENT AND DEBRIS SHALL BE EITHER |
| REMOVED FROM THE CONSTRUCTION SITE OR |
| SECURED IN SUCH A MANNER AS TO MINIMIZE |
| THE DANGER OF SUCH CONSTRUCTION |
| MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| DAMAGE TO PERSONS OR PROPERTY FROM HIGH |
| WINDS. |
| ANY PERSONS WHO FAILS TO COMPLY TO |
| REMOVE OR SECURE THE CONSTRUCTION |
| MATERIALS EQUIPMENT AND DEBRIS WITHIN |
| 24 HRS AFTER A HURRICANE WATCH HAS BEEN |
| ISSUED SHALL BE SUBJECT TO A FINE NOT TO |
| EXCEED $500.00. |
| IN ADDITION TO THE ABOVE, A LICENSED |
| CONTRACTOR WHO VIOLATES THIS SECTION |
| SHALL BE SUBJECT TO DISCIPLINE PURSUANT |
| TO SECTION 113 OF THIS CHAPTER. |