Plan Review Notes
Plan Review Notes For Permit 06080421
Permit Number 06080421
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-16 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE COVER SHEETS
 REFERENCES A "204" LS CODE / NFPA-101.
 THIS SEEMS TO BE A MISPRINT. PLEASE SEE
 THAT PLANS FOR ELECTRICAL AND "A" SHEETS
 RELFECT THE FOLLOWING CODES AT A MIN.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101
  
 2) NOTE: PLEASE SEE IT IS UNCLEAR IF
 THIS WORK IS PART OF A LARGER TENANT
 SPACE WHICH IS STILL PART OF THE SAME
 TENANT OCCUPANCY. PLEASE SEE SPACE AS
 SHOWN SEEMS TO BE PART OF OTHER AREAS
 BUT UNCLEAR ATTHIS TIME. THERE SEEMS
 TO BE RECEPTS AND LTS WHICH MAY BE PART
 OF ANOTHER TENANT, YET SHOWS BEING FED
 FROM THIS TENANT.
 PLEASE CLARIFY.
  
 3) NOTE: PLEASE KNOW IF THIS IS A NEW
 BUILD OUT FOR A NEW TENANT, PLEASE SEE
 FBC CHAPTER 13, 13-415.1.ABC.1.2, .1.2
 AND .1.3 FOR CONTROL OF LIGHTING.
  
 4) NOTE: PLEASE KNOW PLANS MENTIONS 4TH
 FLR, YET THERE SHOULD BE SOME SORT OF
 SUITE/UNIT NUMBER FOR TENANT.
 PLEASE KNOW PLANS WILL BE REVIEWED BY
 THE ADDRESSING REVIEWER AND ONCE A SUITE
 # IS VERIFIED, PLEASE PLACE THAT NUMBER
 ON SAID PLANS.
 FAC 61G1-16.004
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  