Plan Review Notes For Permit 06080338 |
Permit Number |
06080338 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-15 00:00:00 | | | | | NONCOMPLIANT | | | | THE ARCHITECTURAL FIRM MUST DISPLAY THE | | CERTIFICATE OF AUTHORIZATION ON THE | | TITLE BLOCK PER 481.221 (8). | | | | PLEASE INDICATE PANEL DESIGNATION AND | | BRANCH CIRCUIT NUMBERS FOR ALL FACADE | | LIGHTING | | | | IF THE SIGNS REPRESENTED ON SHEET "A2" | | ARE ILLUMINATED, INDICATE COMPLIANCE | | WITH BRANCH CIRCUITING PER 600.5 AND | | DISCONNECTING MEANS PER 600.6. | | | | PLEASE NOTE AN ELECTRICAL CONTRACTOR | | MUST OBTAIN A PERMIT FOR ANY DEMOLITION | | AFFECTING THE ELECTRICAL SYSTEM. | | | | WILLIAM R TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/561) 805-6731 |
|