2006-08-16 00:00:00 | |
| |
| DENIED |
| |
| 1) A CERTIFICATE OF AUTHORIZATION SHALL |
| BE REQUIRED FOR A CORPORATION, LIMITED |
| LIABILITY COMPANY, OR PARTNERSHIP, |
| OFFERING ARCHITECTURAL SERVICES TO THE |
| PUBLIC JOINTLY OR SEPARATELY. |
| PER 481.219(2) F.S. |
| |
| 2) PROVIDE OCCUPANCY AND CONSTRUCTION |
| TYPE PER 106.3.5 FBC* |
| |
| 3) PROVIDE WIND DESIGN DATA ON DRAWINGS |
| PER 1603.1.4 FBC PLEASE INCLUDE THE |
| COMPONENT AND CLADDING PRESSURES FOR THE |
| OPENINGS |
| |
| 4) THE PERMIT APPLICATION SHALL INCLUDE |
| TWO COPIES OF EACH PRODUCT APPROVAL THAT |
| IS RELEVANT PER 9B-72. THESE SHOULD |
| INCLUDE THE FLORIDA STATE APPROVAL COVER |
| PAGES, AND THE PRODUCT NOA THAT LISTS |
| THE SYSTEM COMPONENTS/ FASTENER LIST |
| PAGES, THE PAGES WITH THE CHOSEN |
| ASSEMBLY/ SYSTEM TO BE USED AND THE |
| GENERAL LIMITATIONS PAGE. ALL CAN BE |
| FOUND ON WWW.FLORIDABUILDING.ORG |
| |
| ***NOTE PRODUCT APPROVALS ARE REQUIRED |
| FOR DOORS, WINDOWS, STOREFRONTS, AND NEW |
| ROOF COVERING*** |
| |
| 5) THOSE PRODUCTS WHICH ARE REGULATED BY |
| DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| |
| 6) WINDOWS AND DOORS UP TO 30 FT ABOVE |
| GRADE REQUIRED TO BE LARGE MISSILE |
| IMPACT RESISTANT OR REQUIRE SHUTTERS |
| (PLEASE SEE CITY THAT IS ENCLOSED AS |
| THEIR ARE MORE REQUIREMENTS IF SHUTTERS |
| ARE USED) |
| |
| 7) PROVIDE SIZES FOR WINDOWS AND DOORS |
| TO BE REPLACED TO CONFIRM DESIGN |
| PRESSURES WITH PRODUCT APPROVAL |
| PRESSURES |
| |
| 8) PROVIDE INFORMATION ON BUCK |
| ATTACHMENT |
| |
| 9) PROVIDE BLOCK INFILL ATTACHMENT |
| INFORMATION |
| |
| 10) SIGNS REQUIRE SEPERATE PERMIT |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |