Plan Review Notes
Plan Review Notes For Permit 06080308
Permit Number 06080308
Review Stop P
Sequence Number 3
Notes
Date Text
2007-07-13 13:09:23DENIED 3RD TIME
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THESE PREVIOUS PLUMBING PLAN REVIEW COMMENTS WERE NOT
 ADDRESSED ON THIS RESUBMITTAL:
  
 1. THEWASHING MACHINE ON SHEET 1 OF 4 IS BEING
 INDICATED AS BEING RELOCATED TO THE EXISTING KITCHEN.
 THIS NEEDS TO BE INDICATED ON THE RESUBMITTED SANITARY
 PLUMBING RISER DIAGRAM. THE FOLLOWING IS REQUIRED FOR
 THE WASHING MACHINE ON THE RESUBMITTAL.
 A) PER FBC-2004 PLUMBING, SECTION 909.1 THE WASHING
 MACHINE SHALL DISCHARGE DOWNSTREAM OF THE WET VENTED
 BATHROOM GROUP.
 B) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 C) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE STANDPIPE ON DRAWING.
 D) 708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL
 CLEANOUTS. CLEANOUTS FOR WASHING MACHINES SHALL BE
 LOCATED FOUR FEET (4') ABOVE FINNISH FLOOR (AFF) PLEASE
 INDICATE THE WASHING MACHINE CLEANOUT LOCATION ON THE
 RESUBMITTAL.
 E) 708.7 MINIMUM SIZE. CLEANOUTS SHALL BE THE SAME
 NOMINAL SIZE AS THE PIPE THEY SERVE UP TO 4 INCH.
 CLEANOUT FOR THE WASHING MACHINE SHALL BE 3 INCH.
  
 2. PLEASE INDICATE THE NEW LOCATION OF THE WATER
 HEATER ON THE RESUBMITTED PROPOSED FLOOR PLAN. PLEASE
 INDICATE IF THE WATER HEATER IS GAS OR ELECTRIC ON THE
 RESUBMITTAL.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING IN RED INK FOR
 REFERENCE FOR RESUBMITTAL.(SEE SHEET 1 FOR THESE
 CORRECTIONS.)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]