2007-07-13 13:09:23 | DENIED 3RD TIME |
| REFERENCE: |
| ** FBC-2004 PLUMBING. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THESE PREVIOUS PLUMBING PLAN REVIEW COMMENTS WERE NOT |
| ADDRESSED ON THIS RESUBMITTAL: |
| |
| 1. THEWASHING MACHINE ON SHEET 1 OF 4 IS BEING |
| INDICATED AS BEING RELOCATED TO THE EXISTING KITCHEN. |
| THIS NEEDS TO BE INDICATED ON THE RESUBMITTED SANITARY |
| PLUMBING RISER DIAGRAM. THE FOLLOWING IS REQUIRED FOR |
| THE WASHING MACHINE ON THE RESUBMITTAL. |
| A) PER FBC-2004 PLUMBING, SECTION 909.1 THE WASHING |
| MACHINE SHALL DISCHARGE DOWNSTREAM OF THE WET VENTED |
| BATHROOM GROUP. |
| B) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| WASHER SHALL BE A MINIMUM OF 2 INCHES |
| (51MM) IN DIAMETER. THE AUTOMATIC |
| CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| STACK A MINIMUM OF 3 INCHES (76MM) IN |
| DIAMETER. |
| C) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| TRAPPED. STANDPIPES SHALL |
| EXTEND A MINIMUM OF 18 INCHES (457MM) |
| AND A MAXIMUM OF 42 INCHES (1066MM) |
| ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| PROVIDED TO ALL STANDPIPES AND DRAINS |
| FOR RODDING. PLEASE INDICATE STANDPIPE ON DRAWING. |
| D) 708.9 ACCESS. ACCESS SHALL BE PROVIDED TO ALL |
| CLEANOUTS. CLEANOUTS FOR WASHING MACHINES SHALL BE |
| LOCATED FOUR FEET (4') ABOVE FINNISH FLOOR (AFF) PLEASE |
| INDICATE THE WASHING MACHINE CLEANOUT LOCATION ON THE |
| RESUBMITTAL. |
| E) 708.7 MINIMUM SIZE. CLEANOUTS SHALL BE THE SAME |
| NOMINAL SIZE AS THE PIPE THEY SERVE UP TO 4 INCH. |
| CLEANOUT FOR THE WASHING MACHINE SHALL BE 3 INCH. |
| |
| 2. PLEASE INDICATE THE NEW LOCATION OF THE WATER |
| HEATER ON THE RESUBMITTED PROPOSED FLOOR PLAN. PLEASE |
| INDICATE IF THE WATER HEATER IS GAS OR ELECTRIC ON THE |
| RESUBMITTAL. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: ONLY ONE CORRECTED DRAWING IN RED INK FOR |
| REFERENCE FOR RESUBMITTAL.(SEE SHEET 1 FOR THESE |
| CORRECTIONS.) |
| |
| END OF COMMENTS: |
| |