Plan Review Notes For Permit 06080306 |
Permit Number |
06080306 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-25 00:00:00 | ***DENIED*** | | | | 1) PLEASE SHOW LOCATION OF 2A-10B,C | | RATED FIRE EXTINGUISHER(S). | | | | 2) PLEASE CLARIFY THE USE OF THE NEW | | MIXING ROOM. NOTE (1) ON SHT 1.1 | | REFERENCES MIXING PAINT. PLEASE INDICATE | | MATERIALS AND OR CHEMICALS THAT WILL BE | | USED IN REFERENCED ROOM. | | | | 3) IN ADDITION TO APPLICABE BUILDING | | CODES, LIFE SAFETY SHALL COMPLY WITH | | NFPA 101, 2003 EDITION. | | | | 4) SEPARATE SHOP DRAWINGS AND PERMIT MAY | | BE REQUIRED FOR FIRE SPRINKLER REMODEL. | | PLEASE INDICATE HOW EXISTING FIRE | | SPRINKLER SYSTEM WILL BE IMPACTED. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|