Plan Review Notes For Permit 06080304 |
Permit Number |
06080304 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-07-05 07:08:56 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1 } DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED | | PER 230.70(A)(1) UNLESS THE FEED FROM THE METER TO THE | | PANEL IS UNDERGROUND. INDICATE LOCATION ON PLAN. | | | | 2} PANELS "B" AND "C" ARE LISTED ON THE PANEL SCHEDULE. | | LOCATE ALL EQUIPMENT ON THE PLAN. | | | | 3} PER 110.9 AND 110.10: OBTAIN THE | | AVAILABLE FAULT CURRENT AT THE UTILITY | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | INDICATE THE AIC RATING FOR THE | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | THE AVAILABLE FAULT. | | | | 4} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE | | AND AMPERE RATING, MAIN LUG OR MAIN BREAKER. | | | | 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, | | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE | | CALCULATION GIVEN INDICATES MORE LOAD OPN THE NUETRAL | | THAN ON THE UNGROUNDED CONDUCTORS, WHICH CANNOT BE | | CORRECT. | | | | 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 | | FS, RESPECTIVELY. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] | | | | |
|