2007-07-05 07:08:56 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1 } DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70(A)(1) UNLESS THE FEED FROM THE METER TO THE
 PANEL IS UNDERGROUND. INDICATE LOCATION ON PLAN.
  
 2} PANELS "B" AND "C" ARE LISTED ON THE PANEL SCHEDULE.
 LOCATE ALL EQUIPMENT ON THE PLAN.
  
 3} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4} GIVE PANEL SPECIFICATIONS, NUMBER OF SPACES, VOLTAGE
 AND AMPERE RATING, MAIN LUG OR MAIN BREAKER.
  
 5} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III,
 STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. THE
 CALCULATION GIVEN INDICATES MORE LOAD OPN THE NUETRAL
 THAN ON THE UNGROUNDED CONDUCTORS, WHICH CANNOT BE
 CORRECT.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  