Plan Review Notes For Permit 06080304
Permit Number 06080304
Review Stop B
Sequence Number 3
Notes
Date Text
2007-07-10 15:33:34BUILDING REVIEW 3RD CHECKLIST:
  
 1- NOTICE OF COMMENCEMENT WAS RECORDED ON 03/02/07. PER
 FLORIDA STATUTE SEC. 713.13IT EXPIRES AFTER 90 DAYS
 OF RECORDING IF WORK IS NOT STARTED. THEREFORE, NEED TO
 RE-RECORD THE NOTICE OF COMMENCEMENT AND RE-SUBMIT TO
 THIS OFFICE.
  
 2- FLOOD ELEVATION CERTIFICATE SUBMITTED IS NOT
 REQUIRED FOR A BUILDING LOCATED IN A "C" FLOOD ZONE.
  
 3- NEED TO PROVIDE THE ENERGY CALCULATIONS AS REQUIRED
 BY SEC. 13-600 FBC 2004.
 ***NOTE:MAKE SURE 2006 REVISED FORM IS USED.
  
 4- NOW IS NOT CLEAR IF WINDOWS WITH IMPACT GLAZING WILL
 BE USED OR IF STORM PANELS WILL BE USED. BOTH PRODUCT
 APPROVALS WERE SUBMITTED.SUBMIT ONLY PRODUCT APPROVAL
 FOR EITHER ONE.
 IF USING STORM SHUTTERS THEN, COMPLETE INSTALLATION
 SCHEDULE SHOWING SPECIFICMOUNTING CONDITIONS AND
 ANCHOR TYPE AND SPACING TO BE USED WILL BE REQUIRED.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 5- PLANS NOW SHOW ROOF SHINGLES INSTEAD OF FLAT ROOF
 ASSEMBLY.
 THEN, AS REQUIRED BY DCA RULE 9B-72 NEED TO PROVIDE
 PRODUCT APPROVAL FOR SHINGLES TO BE INSTALLED.
  
 6-SHINGLES PRODUCT APPROVAL TO BE REVIEWED AND
 APPROVE IN WRITING BY ENGINEER OF RECORD AS REQUIRED BY
 SEC. 106.3.3CITY AMENDMENTS TO FBC 2004.
  
 7- ROOF PITCH WAS REVISED TO HAVE 2:12 PITCH.
 THEREFORE,NEED TO SPECIFY TWO LAYERS OF UNDERLAYMENT
 AS REQUIRED BY SEC. R905.2.2 OF 2004 FLORIDA
 RESIDENTIAL CODE ALONG WITH 2006 REVISIONS.
  
 8- SHEET 4:
 A) SPECIFY SIZE (HOW LONG) ARE THE ANCHOR BOLTS USED
 TO SUPPORT WALL LEDGER TO EXISTING WALL. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 B) SPECIFY HOW IS THEROOF GOING TO HAVE CROSS
 VENTILATION'S AS REQUIRED BY SEC. R806 OF 2004 FLORIDA
 RESIDENTIAL CODE.R-19 INSULATION DOESN'T ALLOW AN AIR
 GAP SPACINGFOR CROSS VENTILATION IF IT'S INSTALLED IN
 A 2X6 JOIST.SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 REVISE AS REQUIRED.
  
 C) SPECIFY SIZE (HOW LONG) ARE THE BOLTS FOR
 CONNECTORS HTT22 SPECIFIED ON TYPICAL WALL SECTION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 ANDSIMPSON
 CATALOG.
  
 9- REVISE ROOF SHEATHING MINIMUM TYPE OF NAIL TO BE
 USED. NEED TO USEMIN. 8D RING SHANK NAILS.SEE 2006
 REVISED SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL
 CODE AND REVISE PLANS AS REQUIRED.
  
 10- WHYDID ENGINEER SIGNED PLANS WITH 8/16/07 DATE?.
  
  
 ***NOTE: ONE COPY OF THESE PLANS WILL BE RETAINED IN
 THIS OFFICE TO BE SENT TO THE BOARD OF ENGINEERS FOR
 REVIEW.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712