2006-09-15 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 2- BRING DRAWINGS TO PALM BEACH COUNTY |
| FOR IMPACT FEES. BRING BACK STAMPED |
| DRAWINGS AND COPY OF PAID RECEIPT. |
| |
| 3- A) SURVEY NOTE #8 STATES THAT THIS |
| SURVEY CAN NOT BE USED FOR CONSTRUCTION |
| PURPOSES. PROVIDE REVISED SURVEY. |
| B) FLOOD ZONE IS "C" NOT X N/A. REVISE |
| SURVEY AS REQUIRED. |
| |
| 4- NEED SMOKE DETECTORS AS REQUIRED BY |
| SECTIONS R311.1 AND R313.1.1 OF 2004 |
| RESIDENTIAL CODE. |
| |
| 5- NEED ENERGY CALCULATIONS AS REQUIRED |
| BY CHAPTER 13 FBC 2004. |
| |
| 6- PLANS ARE NOT CLEAR. NEED LEGEND TO |
| IDENTIFY WHICH WALLS ARE NEW, WHICH ARE |
| EXISTING AND WHICH ONES ARE GOING TO BE |
| REMOVED. SECTION 106.1.2 CITY AMENDMENTS |
| TO FBC 2004. |
| |
| 7- NEED TO SPECIFY SIZE OF WINDOWS AND |
| DOORS. SEC. 106.1.2 CITY AMENDMENTS TO |
| FBC 2004. |
| |
| 8- ENGINEER TO SPECIFY ALL DESIGN |
| CRITERIA AS REQUIRED BY SECTION R301 |
| 2004 RESIDENTIAL CODE. |
| |
| 9- SPECIFY ROOF SHEATHING THICKNESS AND |
| FASTENING. SEE TABLE 2304.9.1 FBC 2004. |
| |
| 10- A) PROVIDE COMPLETE INFORMATION FOR |
| STORM SHUTTERS. NEED KEY PLAN AN A |
| COMPLETE INSTALLATION SCHEDULE. SEE |
| ATTACHED INSTALLATION SCHEDULE SAMPLE |
| FROM THE CITY IMPLEMENTATION STANDARD |
| FOR WIND-BORNE DEBRIS IMPACT PROTECTION. |
| B) PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR STORM SHUTTERS. |
| |
| 11- ENGINEER TO IDENTIFY SPECIFIC LEVEL |
| OF ALTERATION THAT APPLIES TO THIS HOUSE |
| AS REQ'D BY SEC. 301.5 0F 2004 FLORIDA |
| EXISTING BUILDING CODE. |
| |
| 12- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) FLAT ROOF SYSTEM. |
| ***NOTE: NEED TO IDENTIFY SPECIFIC FLAT |
| ROOF APPROVED ASSEMBLY AND COMPLY WITH |
| GENERAL LIMITATION #7 OR #9 AS REQUIRED. |
| SEE ATTACHED COPY OF CITY POLICY FOR |
| ROOFING PERMITS. |
| B) ALL STRUCTURAL CONNECTORS SPECIFIED |
| ON PLANS.SEE PLANS AND DETAILS. |
| |
| 13- ENGINEER TO REVIEW AND APPROVE IN |
| WRITTING ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMNTS |
| TO FBC 2004. |
| |
| 14- BUILDING PERMIT VALUATION DECLARED |
| ON THE PERMIT APPLICATION IS |
| UNDERESTIMATED. PROVIDE CORRECT |
| VALUATION OR IT WILL BE ESTIMATED AS |
| DESCRIBED IN SEC. 108.3 CITY AMENDMENTS |
| TO FBC 2004. |
| |
| 15- ONLY TWO SETS OF DRAWINGS AND |
| PRODUCT APPROVALS ARE REQUIRED. |
| |
| 16- TYPICAL WALL SECTION: |
| A) R-30 INSULATION DOESN'T FIT IN 2X6 |
| RAFTERS. REVISE AS REQUIRED. |
| B) R-19 INSULATIONDOESN'T FIT IN 2X4 |
| STUDS. REVISE AS REQUIRED. |
| C) WOOD NEED TO BE MIN. 6" ABOVE GRADE |
| AS REQUIRED BY SEC. R319.1(5). REVISE |
| WALL SECTION AS REQUIRED. |
| D) SPECIFY SIZE OF BOLT SPECIFIED TO |
| ATTACH LEDGER TO EXISTING WALL. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| E) SPECIFY ROOF VENTILATION AS REQUIRED |
| BY SEC. R806 2004 RESIDENTIAL CODE. |
| F) CLARIFY NOTE REGARDING TRUSS |
| ATTACHED WITH MTS12. THERE ARE NOT |
| TRUSSES IN THIS ROOF. REVISE AS |
| REQUIRED. |
| G) PROVIDE DETAIL SHOWING HOW IS THE |
| SIMPSON MSTA12 ATTACHED TO 2X4 STUD AT |
| BOTTOM?. SEC. 106.1.2 CITY AMENDMENTS. |
| |
| 17- WIND LOAD DRAWINGS ON SHEET #3 ARE |
| FOR SLIDING GLASS DOORS AND GARAGE |
| DOORS. THERE ARE NOT THESE TYPES OF |
| DOORS IN THIS PROJECT AND DRAWINGS ARE |
| NOT LEGIBLE. |
| |
| 18- REVISE DOOR AND WINDOW JAMB DETAILS. |
| TYPICAL WALL SECTIONS SPECIFIES 2X4 |
| FRAMING, WHILE DETAILS CALL FOR 2X6. |
| REVISE AS REQUIRED. |
| |
| 19- CONTRACTOR TO UPDATE THE LICENSE |
| RECORDS WITH THE PERMIT CLERK. |
| |