Plan Review Notes For Permit 06080288 |
Permit Number |
06080288 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-09-15 00:00:00 | ***DENIED*** | | | | 1) PRODUCT APPROVALS WILL BE REQUIRED | | FOR THE PROPOSED FUEL TANKS. INFORMATION | | REGARDING THE CONSTRUCTION, FIRE RATING, | | DOCUMENTED LISTINGS OR APPROVALS FROM | | THIRD PARTY TESTING AGENCIES, AND ANY | | APPLICABLE BALLISTIC TESTING RESULTS. | | | | 2) WHO WILL BE RESPONSIBLE FOR FUELING | | OPERATIONS? | | | | 3) IN ADDITION TO NO SMOKING AND STOP | | ENGINE, APPROPRIATE WARNING SIGNS SHALL | | INDICATE THE TYPE OF PORTABLE CONTAINERS | | THAT CAN BE FILLED, AND EMERGENCY SHUT | | OFF WORDING. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|