2006-08-04 00:00:00 | ******** UNSAT ******* |
| |
| 1) NOTE: PLEASE SEE PANELS FOR ALL |
| BRANCH CIRCUITS MAY NOT BE LOCATED IN |
| GARAGE. PLEASE SEE 225.31-225.39. FBC |
| DEFINITIONS OF ONE BUILDING ETC. |
| PLEASE SEE DEISGN AS SHOWN NEEDS TO BE |
| RE-DESIGNED. |
| |
| 2) NOTE: PLEASE SEE 250.32 FOR GROUNDING |
| ELECTRODE SYSTEM WHICH IS NOT SHOWN FOR |
| HOUSE. |
| |
| 3) NOTE: PLEASE SEE PANEL SCHEDULE IS |
| NOT COMPLETE FOR ALL A/C LOADS, OCP, AND |
| CONDUCTOR SIZES. |
| PLEASE CORRELATE WITH MECH PLANS. |
| UNABLE TO VERIFY AT THIS TIME. |
| |
| 4) NOTE: PLEASE SEE PLANS SHALL ALSO |
| REFELCT THE 2002 NFPA-72 . |
| PLEASE SEE LOCATIONS OF SD'S REQUIRED |
| WITHIN 3' OF THE PEAK ON SLOPED CEILING. |
| 11.8.3 |
| |
| 5) NOTE: PLEASE SEE 408.4,PANEL SCHEDULE |
| SHALL BE SPECIFIC FOR ALL CIRCUITS, |
| AREAS/ ROOMS ON PLANS. IE; LIVING RM |
| LTS, HALL LTS, KTICHEN LTS ETC. |
| IT IS KNOWN, THAT DURING CONSTRUCTION |
| THESE WILL MOST LIKELY CHANGE, HOWEVER |
| THESE CAN BE REVISED AT A LATER DATE |
| WITH ANY OTHER REVISONS. |
| FBC 106.1.2 |
| |
| 6) NOTE: PLEASE CLARIFY ONLY TWO ARC |
| FAULT PROTECTED CIRCUITS ARE BEING |
| SHOWN, YET THERE ARE MORE THAN TWO |
| BEDRMS. |
| 210.12B, PLEASE INDICATE OTHER AS |
| CIRCUITS AS SHOWN APPEAR LOADS FOR ALL |
| BEDRMS MAY EXCEED BRANCH CIRCUIT RATING. |
| 240.4, 210.20, 220 |
| |
| 7) NOTE: PLEASE SEE NO DINING RM IS |
| BEING SHOWN, HOWEVER PLEASE SEE |
| BREAKFAST ARE IS ALSO CONSIDERED TO BE |
| PART OF THE CIRCUITING AS REQUIRED PER |
| 210.11C1,210.52B1,220.16. |
| DINING, BRKFST AREAS AND THE LIKE SHALL |
| BE ON ONE OR MORE OF THE REQUIRED. ETC. |
| |
| 8) NOTE: PLEASE VERIFY THE DISOCNNECTING |
| MEANS FOR AHUS', AS THEY DO NOT MEET |
| 110.26. |
| IF DISCONNECTING MEANS IS PART OF UNIT, |
| PLEASE SHOW. |
| |
| 9) NOTE: PLEASE SEE MISSING FOOTER STEEL |
| REQUIRED FOR ALL STRUCTURES WHICH |
| CONTAIN THE ELECTRICAL. |
| PLEASE SEE 250.50,250.32 ETC |
| |
| 10) NOTE: PLEASE SEE LT ABOVE WASHER AND |
| DRYER DOES NOT SEEM TO MEET 410.8 |
| PLEASE SEE SHELVING IS COMMON ABOVE |
| THESE UNITS, AND SPACE FROM 410.8 |
| REQUIRES 18" OUT ETC. |
| PLEASE SEE LT MAY BE ABLE TO BE MOUNTED |
| ABOVE DOOR/ WALL. |
| |
| ** PLEASE KNOW, DUE TO THE DEISGN OF |
| ELECTRICAL SYSTEM AND SUBSTANTIAL |
| CHANGES WHICH WILL BE REQUIRED. THERE |
| MAY BE COMMENTS ON NEXT REVIEW. |
| |
| ** IMPORTANT ** |
| PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| REVISED SHEETS INTO COMPLETE SETS FOR |
| REVIEW AND STAMPING. ONLY ONE SET OF THE |
| OLF/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |