Plan Review Notes
Plan Review Notes For Permit 06080124
Permit Number 06080124
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-04 00:00:00******** UNSAT *******
  
 1) NOTE: PLEASE SEE PANELS FOR ALL
 BRANCH CIRCUITS MAY NOT BE LOCATED IN
 GARAGE. PLEASE SEE 225.31-225.39. FBC
 DEFINITIONS OF ONE BUILDING ETC.
 PLEASE SEE DEISGN AS SHOWN NEEDS TO BE
 RE-DESIGNED.
  
 2) NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM WHICH IS NOT SHOWN FOR
 HOUSE.
  
 3) NOTE: PLEASE SEE PANEL SCHEDULE IS
 NOT COMPLETE FOR ALL A/C LOADS, OCP, AND
 CONDUCTOR SIZES.
 PLEASE CORRELATE WITH MECH PLANS.
 UNABLE TO VERIFY AT THIS TIME.
  
 4) NOTE: PLEASE SEE PLANS SHALL ALSO
 REFELCT THE 2002 NFPA-72 .
 PLEASE SEE LOCATIONS OF SD'S REQUIRED
 WITHIN 3' OF THE PEAK ON SLOPED CEILING.
 11.8.3
  
 5) NOTE: PLEASE SEE 408.4,PANEL SCHEDULE
 SHALL BE SPECIFIC FOR ALL CIRCUITS,
 AREAS/ ROOMS ON PLANS. IE; LIVING RM
 LTS, HALL LTS, KTICHEN LTS ETC.
 IT IS KNOWN, THAT DURING CONSTRUCTION
 THESE WILL MOST LIKELY CHANGE, HOWEVER
 THESE CAN BE REVISED AT A LATER DATE
 WITH ANY OTHER REVISONS.
 FBC 106.1.2
  
 6) NOTE: PLEASE CLARIFY ONLY TWO ARC
 FAULT PROTECTED CIRCUITS ARE BEING
 SHOWN, YET THERE ARE MORE THAN TWO
 BEDRMS.
 210.12B, PLEASE INDICATE OTHER AS
 CIRCUITS AS SHOWN APPEAR LOADS FOR ALL
 BEDRMS MAY EXCEED BRANCH CIRCUIT RATING.
 240.4, 210.20, 220
  
 7) NOTE: PLEASE SEE NO DINING RM IS
 BEING SHOWN, HOWEVER PLEASE SEE
 BREAKFAST ARE IS ALSO CONSIDERED TO BE
 PART OF THE CIRCUITING AS REQUIRED PER
 210.11C1,210.52B1,220.16.
 DINING, BRKFST AREAS AND THE LIKE SHALL
 BE ON ONE OR MORE OF THE REQUIRED. ETC.
  
 8) NOTE: PLEASE VERIFY THE DISOCNNECTING
 MEANS FOR AHUS', AS THEY DO NOT MEET
 110.26.
 IF DISCONNECTING MEANS IS PART OF UNIT,
 PLEASE SHOW.
  
 9) NOTE: PLEASE SEE MISSING FOOTER STEEL
 REQUIRED FOR ALL STRUCTURES WHICH
 CONTAIN THE ELECTRICAL.
 PLEASE SEE 250.50,250.32 ETC
  
 10) NOTE: PLEASE SEE LT ABOVE WASHER AND
 DRYER DOES NOT SEEM TO MEET 410.8
 PLEASE SEE SHELVING IS COMMON ABOVE
 THESE UNITS, AND SPACE FROM 410.8
 REQUIRES 18" OUT ETC.
 PLEASE SEE LT MAY BE ABLE TO BE MOUNTED
 ABOVE DOOR/ WALL.
  
 ** PLEASE KNOW, DUE TO THE DEISGN OF
 ELECTRICAL SYSTEM AND SUBSTANTIAL
 CHANGES WHICH WILL BE REQUIRED. THERE
 MAY BE COMMENTS ON NEXT REVIEW.
  
 ** IMPORTANT **
 PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING. ONLY ONE SET OF THE
 OLF/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717