Plan Review Notes
Plan Review Notes For Permit 06080076
Permit Number 06080076
Review Stop P
Sequence Number 1
Notes
Date Text
2006-08-08 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW ON THE SANITARY
 PLUMBING RISER DIAGRAM ON SHEET A-4.1,
 DETAIL #7.(NOTE: THE FOLLOWING CORREC-
 TIONS ARE IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.)
  
 1. PER FBC-2004, CHAPTER 1, SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.(NOTE: 2ND FLOOR
 LAUNDRY TRAY ROOM #09 MISSING AND NOT
 ALL FIXTURE TRAPS SIZED.)
 2. PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 (NOTE: THE 1ST FLOOR POWDER ROOM #04 AND
 THE 2ND FLOOR LAUNDRY ROOM #09 SANITARY
 ARE PIPED WRONG.)
 3. PER FBC-2004 PLUMBING THE FOLLOWING
 NEEDS TO BE CORRECTED ON THE WASHING
 MACHINE.
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.(NOTE: WASTE STACK SIZED WRONG)
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE
 INDIVIDUALLY TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. (NOTE: PLEASE INDICATE
 STANDPIPE ON DRAWING)
 4. PER FBC-2004 PLUMBING THE FOLLOWING
 NEEDS TO BE INDICATED ON CLEANOUTS.
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK. PLEASE INDICATE ON
 DRAWING.
 5.PER FBC-2004 PLUMBING, SECTION 802.1.6
 DOMESTIC DISHWASHING MACHINES: SHALL
 DISCHARGE INTO A WYE-BRANCH FITTING ON
 THE TAILPIECE OF THE KITCHEN SINK OR THE
 DISHWASHER CONNECTION OF A FOOD WASTE
 GRINDER. PLEASE REFERENCE ISOMETRIC
 DRAWING.
 6. PER FBC-2004 PLUMBING, SECTION 905.5
 HEIGHT ABOVE FIXTURES: A CONNECTION
 BETWEEN A VENT STACK OR STACK VENT SHALL
 BE MADE AT LEAST 6" INCHES ABOVE THE
 FLOOD LEVEL RIM OF THE FIXTURE SERVED BY
 THE VENT.(NOTE: VENT FOR 1ST FLOOR
 POWDER ROOM #04 WRONG)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  