2006-08-09 00:00:00 | ****** DENIED****** |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLUMBING PLAN REVIEW ON THE SANITARY |
| PLUMBING RISER DIAGRAM ON SHEET A-4.1, |
| DETAIL #7. (NOTE: THE FOLLOWING |
| CORRECTIONS ARE IN RED INK ON SHEET |
| A-4.1 DETAIL #7 FOR REFERENCE FOR |
| RESUBMITTAL.) |
| |
| 1. PER FBC-2004, CHAPTER 1, SECTION |
| 106.3.5.4 RESIDENTIAL (ONE AND TWO |
| FAMILY) SUBMIT A PLUMBING SANITARY |
| ISOMETRIC RISER DIAGRAM INDICATING ALL |
| WASTE, VENTS, TRAPS WITH SIZES, AND |
| CLEANOUT LOCATIONS.(NOTE: 2ND FLOOR |
| LAUNDRY TRAY IN ROOM #09 MISSING AND NOT |
| ALL FIXTURE TRAPS SIZED.) |
| 2. PER FBC-2004, PLUMBING, SECTION 909.1 |
| WET VENT PERMITTED: ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH |
| DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT. |
| (NOTE: THE 1ST FLOOR POWDER ROOM #04 AND |
| THE 2ND FLOOR LAUNDRY ROOM #09 SANITARY |
| ARE PIPED WRONG.) |
| 3. PER FBC-2004 PLUMBING THE FOLLOWING |
| NEEDS TO BE CORRECTED ON THE WASHING |
| MACHINE. |
| (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| WASHER SHALL BE A MINIMUM OF 2 INCHES |
| (51MM) IN DIAMETER. THE AUTOMATIC |
| CLOTHES WASHER FIXTURE DRAIN SHALL |
| CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| STACK A MINIMUM OF 3 INCHES (76MM) IN |
| DIAMETER. (NOTE: WASTE STACK SIZED |
| WRONG.) |
| (B) 802.4 STANDPIPES.STANDPIPES SHALL BE |
| INDIVIDUALLY TRAPPED. STANDPIPES SHALL |
| EXTEND A MINIMUM OF 18 INCHES (457MM) |
| AND A MAXIMUM OF 42 INCHES (1066MM) |
| ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| PROVIDED TO ALL STANDPIPES AND DRAINS |
| FOR RODDING. (NOTE: PLEASE INDICATE |
| STANDPIPE ON DRAWING.) |
| 4. PER FBC--2004 PLUMBING THE FOLLOWING |
| NEEDS TO BE INDICATED ON CLEANOUTS. |
| (A) 708.3.4 BASE OF STACK. A CLEANOUT |
| SHALL BE PROVIDED AT THE BASE OF EACH |
| WASTE OR SOIL STACK. PLEASE INDICATE ON |
| DRAWING. |
| 5. PER FBC-2004 PLUMBING, SECTION |
| 802.1.6 DOMESTIC DISHWASHING MACHINES: |
| SHALL DISCHARGE INTO A WYE-BRANCH |
| FITTING ON THE TAILPIECE OF THE KITCHEN |
| SINK OR THE DISHWASHING CONNECTION OF A |
| FOOD WASTE GRINDER. PLEASE REFERENCE |
| ISOMETRIC DRAWING. |
| 6. PER FBC-2004 PLUMBING, SECTION 905.5 |
| HEIGHT ABOVE FIXTURES: A CONECTION |
| BETWEEN A VENT STACK OR STACK VENT SHALL |
| BE MADE AT LEAST 6" INCHES ABOVE THE |
| FLOOD LEVEL RIM OF THE FIXTURE SERVED BY |
| THE VENT. (NOTE: VENT FOR 1ST FLOOR |
| POWDER ROOM #04 WRONG.) |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |