Date |
Text |
2006-08-11 00:00:00 | |
| |
| DENIED |
| |
| 1) BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SETS OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561) 233-5025 FOR MORE |
| INFORMATION |
| |
| 2) THE CLAIMED VALUATION ON THE PERMIT |
| APPLICATION IS LOW. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| COST EXCLUDING LAND VALUE. OUR VALUATION |
| REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| AND MEANS COST ANALYSIS SERVICES PER |
| 108.3 FBC* |
| |
| 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| COMPLY WITH R802.10.1 FBC WITH PERMIT |
| APPLICATION OR BEFORE INSTALLATION THAT |
| HAVE BEEN REVIEWED AND APPROVED BY THE |
| DESIGNER OF RECORD |
| |
| 4) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| FBC. BE SURE THAT THEY ARE SIGNED AND |
| DATED BY PREPARER AND OWNER/AGENT PRIOR |
| TO SUBMITTAL |
| |
| 5) AN ENGINEER PRACTICING THROUGH A DULY |
| AUTHORIZED ENGINEERING BUSINESS SHALL |
| INDICATE THEIR NAME AND LICENCE #, AS |
| WELL AS THE NAME,ADDRESS AND CERTIFICATE |
| OF AUTHORIZATION #ON EACH SHEET PER |
| 61G15-23.002 (2) FAC |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| 6) THE FOLLOWING PRODUCT APPROVALS |
| REQUIRE CORRECTIONS |
| |
| A) SINGLE I/S ENTRY DOOR IS NOT APPROVED |
| UNDER THE 2004 STATE PRODUCT |
| APPROVALS.PLEASE SEE THAT THE ONLY STEEL |
| EDGE DOOR DOES NOT HAVE IMPACT RATING |
| BUT FIBERGLASS IMPACT DOORS ARE UNDER FL |
| #4334 |
| B) NO PRODUCT APPROVALS WERE SUBMITTED |
| FOR SLIDING GLASS DOOR |
| C) PROVIDE UPDATED PRODUCT APPROVALS FOR |
| ROOF COVERING (NOA HAS BEEN REVISED) |
| D) "WINDLOAD 188" OVERHEAD GARAGE DOOR |
| NOT LISTED ON STATE, WILL ACCEPT |
| MIAMI-DADE FOR LOCAL PRODUCT APPROVAL |
| E) PROVIDE PRODUCT APPROVALS FOR PRE |
| CAST LINTELS AND WOOD CONNECTORS/ANCHOR |
| (FOR CONNECTORS INDEX WITH FL#'S IS |
| ADEQUATE SEE ATTACHED INDEX COVER) |
| F) PROVIDE INSTALLATION SCHEDULE, KEY |
| PLAN AND PRODUCT APPROVALS FOR IMPACT |
| PROTECTIVE SHUTTERS |
| |
| 7) REMOVE ALL NON USED PRODUCT APPROVAL |
| FROM SUBMITTALS |
| |
| 8) PROVIDE A SITE PLAN THAT SHOWS |
| DRAINAGE IN COMPLIANCE WITH THE |
| REQUIREMENTS OF R403.1 |
| |
| 9) ROOF SHEATHING NAIL PATTERN ON S-3 TO |
| MEET THE REQUIREMENTS OF 2304.9.1 FBC |
| |
| 10) PROVIDE CONNECTORS AND UPLIFT FOR |
| PATIO ROOF TRUSSES ON S-2 |
| |
| 11) DOOR BETWEEN HOUSE AND GARAGE SHALL |
| MEET THE REQUIREMENTS OF R309.1 FBC |
| |
| 12) WINDOW ABOVE TUB DECK AND ANY |
| GLAZING BETWEEN TUB AND SHOWER SHALL BE |
| CONSIDERED GLAZING IN A HAZARDOUS |
| LOCATION PER R308.4 PLEASE SPECIFY |
| TEMPERED GLASS ON DRAWINGS |
| |
| 13) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |
| BLDG PLAN REVIEW |
| ADRIAN MORSE |
| 561-805-6716 |
| |
| |
| |
| |
| |
| |