Plan Review Notes
Plan Review Notes For Permit 06080074
Permit Number 06080074
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-11 00:00:00 
  
 DENIED
  
 1) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION
  
 2) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE
 DESIGNER OF RECORD
  
 4) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 5) AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC
  
  
  
  
  
  
  
  
  
  
 6) THE FOLLOWING PRODUCT APPROVALS
 REQUIRE CORRECTIONS
  
 A) SINGLE I/S ENTRY DOOR IS NOT APPROVED
 UNDER THE 2004 STATE PRODUCT
 APPROVALS.PLEASE SEE THAT THE ONLY STEEL
 EDGE DOOR DOES NOT HAVE IMPACT RATING
 BUT FIBERGLASS IMPACT DOORS ARE UNDER FL
 #4334
 B) NO PRODUCT APPROVALS WERE SUBMITTED
 FOR SLIDING GLASS DOOR
 C) PROVIDE UPDATED PRODUCT APPROVALS FOR
 ROOF COVERING (NOA HAS BEEN REVISED)
 D) "WINDLOAD 188" OVERHEAD GARAGE DOOR
 NOT LISTED ON STATE, WILL ACCEPT
 MIAMI-DADE FOR LOCAL PRODUCT APPROVAL
 E) PROVIDE PRODUCT APPROVALS FOR PRE
 CAST LINTELS AND WOOD CONNECTORS/ANCHOR
 (FOR CONNECTORS INDEX WITH FL#'S IS
 ADEQUATE SEE ATTACHED INDEX COVER)
 F) PROVIDE INSTALLATION SCHEDULE, KEY
 PLAN AND PRODUCT APPROVALS FOR IMPACT
 PROTECTIVE SHUTTERS
  
 7) REMOVE ALL NON USED PRODUCT APPROVAL
 FROM SUBMITTALS
  
 8) PROVIDE A SITE PLAN THAT SHOWS
 DRAINAGE IN COMPLIANCE WITH THE
 REQUIREMENTS OF R403.1
  
 9) ROOF SHEATHING NAIL PATTERN ON S-3 TO
 MEET THE REQUIREMENTS OF 2304.9.1 FBC
  
 10) PROVIDE CONNECTORS AND UPLIFT FOR
 PATIO ROOF TRUSSES ON S-2
  
 11) DOOR BETWEEN HOUSE AND GARAGE SHALL
 MEET THE REQUIREMENTS OF R309.1 FBC
  
 12) WINDOW ABOVE TUB DECK AND ANY
 GLAZING BETWEEN TUB AND SHOWER SHALL BE
 CONSIDERED GLAZING IN A HAZARDOUS
 LOCATION PER R308.4 PLEASE SPECIFY
 TEMPERED GLASS ON DRAWINGS
  
 13) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  