2006-08-09 00:00:00 | |
| |
| DENIED |
| |
| 1) BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SETS OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561) 233-5025 FOR MORE |
| INFORMATION |
| |
| 2) THE CLAIMED VALUATION ON THE PERMIT |
| APPLICATION IS LOW. FOR PERMITTING |
| PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT |
| COST EXCLUDING LAND VALUE. OUR VALUATION |
| REFERENCE IS ICC (BVD), MARSHALL-SWIFT |
| AND MEANS COST ANALYSIS SERVICES PER |
| 108.3 FBC* |
| |
| 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| COMPLY WITH R802.10.1 FBC WITH PERMIT |
| APPLICATION OR BEFORE INSTALLATION THAT |
| HAVE BEEN REVIEWED AND APPROVED BY THE |
| DESIGNER OF RECORD |
| |
| 4) SUBMIT ENERGY CALC'S PER 13-101.2.2 |
| FBC. BE SURE THAT THEY ARE SIGNED AND |
| DATED BY PREPARER AND OWNER/AGENT PRIOR |
| TO SUBMITTAL |
| |
| 5) MAKE CORRECTIONS TO WIND DESIGN DATA |
| AND DESIGN LOAD SHEDULE TO COMPLY WITH |
| THE 2004 FBC AND APPLICABLE SECTIONS ON |
| 3.1 |
| |
| 6) CLARIFY PORCH SUPPORT DETAIL "D" IS |
| THE SUPPORT IN THE CENTER OV\F EACH |
| INDIVIDUAL BEAM SPAN OR THE CENTER OF |
| THE 2 SPANS? IF IN LOCATION SHOWN NO |
| FOUNDATIONS ARE PRESENT. IF NOT ARE THE |
| BEAM SPANS FOR (2) 2X10 OF APPROX |
| 11'-10" OK? |
| |
| 7) PROVIDE ATTACHMENT TYPE AND AMOUNT |
| FOR HU210-2 BEAM HANGERS, MAY ALSO |
| REQUIRE CONCEALED FLANGE TYPE ON CORNERS |
| |
| 8) PROVIDE LINTEL SCHEDULE THAT CMPLIES |
| WITH 2104.1.5 FBC |
| |
| 9) THE FOLLOWING PRODUCT APPROVALS |
| REQUIRE CORRECTIONS |
| |
| A) SINGLE AND DOUBLE O/S GLAZED ENTRY |
| DOORS ARE NOT APPROVED UNDER THE 2004 |
| STATE PRODUCT APPROVALS.PLEASE SEE THAT |
| THE ONLY STEEL EDGE DOOR THAT IS GLAZED |
| DOES NOT HAVE IMPACT RATING BUT GLAZED |
| FIBERGLASS IMPACT DOORS ARE UNDER FL |
| #4334 |
| B) H-R MULLION PRODUCT APPROVALS ARE |
| RE-COPIED TO MANY TIMES AND CANNOT BE |
| READ PLEASE REPRINT |
| C) GAF SHINGLES HAVE CORRECT STATE COVER |
| SHEET BUT THE NOA HAS BEEN REVISED |
| PLEASE SUBMIT NEW NOA |
| D) "WINDLOAD 188" OVERHEAD GARAGE DOOR |
| NOT LISTED ON STATE, WILL ACCEPT |
| MIAMI-DADE FOR LOCAL PRODUCT APPROVAL |
| E) PROVIDE PRODUCT APPROVALS FOR PRE |
| CAST LINTELS AND WOOD CONNECTORS/ANCHOR |
| (FOR CONNECTORS INDEX WITH FL#'S IS |
| ADEQUATE SEE ATTACHED INDEX COVER) |
| |
| 10) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |