Plan Review Notes
Plan Review Notes For Permit 06080061
Permit Number 06080061
Review Stop E
Sequence Number 3
Notes
Date Text
2007-01-07 10:54:32** UNSAT 3RD REVIEW **
  
  
 1) NOTE: PLEASE PROVIDE CALCULATIONS AS REQUESTED ON
 THE TWO PREVIOUS REVIEWS. RESPONSE LETTER MENTIONS TO
 SEE SHEET A-7, HOWEVER SHEET A-7 ONLY SHOWS THE PANEL
 SCHEDULE AND SOME CONNECTED LOADS. PLEASE SEE 220.3,
 220.10, 220.11 220.13 ETC
 ALL CONTINUOUS LOADS PER 215.3, 230.42
  
 2) NOTE:PLEASE SEE 220.3(B)(7) AND 220.12(A) FOR
 INFORMATION REGARDING LOAD COMPUTATIONS FOR SHOW
 WINDOWS. PLEASE SEE HOW LOADS SHALL BE FIGURED FOR
 BRACNH CIRCUITS AND FOR FEEDERS. PLEASE SEE THERE IS NO
 BREAK DOWN OR INFORMATION REGARDING LOADS ON WINDOWS
 AND HOW THESE LOADS WERE DERIVED.
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW AS THE 2ND SET OF
 PLANS WHICH CAME IN CONTAIN A COMPLETELY NEW RISER
 THERE WERE NEW COMMENTS. PLEASE SEE THAT IS WAS
 REQUESTED TO SUBMIT THE MANUFACTURES SPECS/CUT SHEETS
 FOR THE EMERGENCY PANEL/MTS WHICH WAS BEING INSTALLED.
 PLEASE SEE THERE ARE SPEC SHEETS IN THE PACKAGE HOWEVER
 THEY ARE FOR COUNTLESS PANELS AND EQUIPMENT. PLEASE
 ONLY SUBMIT THAT WHICH CORRELATES TO PLANS AND THAT
 WHICH IS RELEVANT TO THIS INSTALLATION. PANELS AND
 SPECS FOR ALL THE OTHERS AS SUBMITTED WILL HAVE NO
 BEARING ON THIS JOB.
 110.3, 90.7.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW FOR REQUIRED
 DISCONNECTING MEANS FOR THE FEED FROM THE GEN.IF IN
 AN EMERGENCY THE GENERATOR IS RUNNING AND CAN NOT BE
 SHUT OFF, WHEN MAINS AND DISCONNECTING MEANS ARE NOT
 GROUPED, UNPLUGGING THE GENERATOR WHILE UNDER LOAD IS
 NOT PERMITTED AND IS A SAFETY ISSUE FOR ANY PERSONNEL.
 PLEASE SEE NOTE#7 ON A-6 STILL MENTIONS ALL ELECTRICAL
 PANELS AND SERVICEEQUIPMENT IS EXISTING, YET PLANS
 SHOW MANY OF THESE ITEMS AS NEW?
 PLEASE CORRELATE NOTES, PLANS, RISER, PANELS ETC.
 225.31-225.39, 230.72
  
 5) NOTE: PLEASE KNOW IT HAS BEEN DISCOVERED SINCE THE
 LAST REVIEW THIS IS A BUILD OUT OF WHAT USED TO BE AN
 OLD SERVICE GARAGE AND WOULD BE A CHANGE IN OCCUPANCY.
  
 PLEASE SUBMIT ENERGY CALCULATIONS PER 2004 FBC.
 13-415.1.AB.1
 THIS WAS NOT PREVIOUSLY REQUESTED AS THIS WAS APPLIED
 AS EXISTING CAR SALES OFFICE AND EXISTING TENANT FOR
 SAME USE.
  
 6) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR
 CODE COMPLIANCE. PLEASE SEE A FEE OF $2100.00 HAS NOW
 BEEN ASSESSED TO THE DESIGN PROFESSIONAL AS REQUIRED
 PER THE FLORIDA STATUTES AS GIVEN. THIS FEE IS BEING
 ADDED TO THEEXISTING 4X FEE FOR STARTING WORK WITHOUT
 PERMITS WHICH WAS ALREADY ADDED TO THIS JOB. PLEASE SEE
 THIS FEE IS REQUIRED TO BE PAID BEFORE RESUBMITTING OF
 PLANS FOR THE NEXT REVIEW. PLEASE ALSO KNOW ONE SET OF
 EACH OF THE PLANS ARE BEING RETAINED BY THIS OFFICE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-06 20:09:502007-01-06 20:09:50
 IN ELEC FOR REVIEW