Date |
Text |
2007-01-07 10:54:32 | ** UNSAT 3RD REVIEW ** |
| |
| |
| 1) NOTE: PLEASE PROVIDE CALCULATIONS AS REQUESTED ON |
| THE TWO PREVIOUS REVIEWS. RESPONSE LETTER MENTIONS TO |
| SEE SHEET A-7, HOWEVER SHEET A-7 ONLY SHOWS THE PANEL |
| SCHEDULE AND SOME CONNECTED LOADS. PLEASE SEE 220.3, |
| 220.10, 220.11 220.13 ETC |
| ALL CONTINUOUS LOADS PER 215.3, 230.42 |
| |
| 2) NOTE:PLEASE SEE 220.3(B)(7) AND 220.12(A) FOR |
| INFORMATION REGARDING LOAD COMPUTATIONS FOR SHOW |
| WINDOWS. PLEASE SEE HOW LOADS SHALL BE FIGURED FOR |
| BRACNH CIRCUITS AND FOR FEEDERS. PLEASE SEE THERE IS NO |
| BREAK DOWN OR INFORMATION REGARDING LOADS ON WINDOWS |
| AND HOW THESE LOADS WERE DERIVED. |
| |
| 3) NOTE: PLEASE SEE PREVIOUS REVIEW AS THE 2ND SET OF |
| PLANS WHICH CAME IN CONTAIN A COMPLETELY NEW RISER |
| THERE WERE NEW COMMENTS. PLEASE SEE THAT IS WAS |
| REQUESTED TO SUBMIT THE MANUFACTURES SPECS/CUT SHEETS |
| FOR THE EMERGENCY PANEL/MTS WHICH WAS BEING INSTALLED. |
| PLEASE SEE THERE ARE SPEC SHEETS IN THE PACKAGE HOWEVER |
| THEY ARE FOR COUNTLESS PANELS AND EQUIPMENT. PLEASE |
| ONLY SUBMIT THAT WHICH CORRELATES TO PLANS AND THAT |
| WHICH IS RELEVANT TO THIS INSTALLATION. PANELS AND |
| SPECS FOR ALL THE OTHERS AS SUBMITTED WILL HAVE NO |
| BEARING ON THIS JOB. |
| 110.3, 90.7. |
| FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| |
| 4) NOTE: PLEASE SEE PREVIOUS REVIEW FOR REQUIRED |
| DISCONNECTING MEANS FOR THE FEED FROM THE GEN.IF IN |
| AN EMERGENCY THE GENERATOR IS RUNNING AND CAN NOT BE |
| SHUT OFF, WHEN MAINS AND DISCONNECTING MEANS ARE NOT |
| GROUPED, UNPLUGGING THE GENERATOR WHILE UNDER LOAD IS |
| NOT PERMITTED AND IS A SAFETY ISSUE FOR ANY PERSONNEL. |
| PLEASE SEE NOTE#7 ON A-6 STILL MENTIONS ALL ELECTRICAL |
| PANELS AND SERVICEEQUIPMENT IS EXISTING, YET PLANS |
| SHOW MANY OF THESE ITEMS AS NEW? |
| PLEASE CORRELATE NOTES, PLANS, RISER, PANELS ETC. |
| 225.31-225.39, 230.72 |
| |
| 5) NOTE: PLEASE KNOW IT HAS BEEN DISCOVERED SINCE THE |
| LAST REVIEW THIS IS A BUILD OUT OF WHAT USED TO BE AN |
| OLD SERVICE GARAGE AND WOULD BE A CHANGE IN OCCUPANCY. |
| |
| PLEASE SUBMIT ENERGY CALCULATIONS PER 2004 FBC. |
| 13-415.1.AB.1 |
| THIS WAS NOT PREVIOUSLY REQUESTED AS THIS WAS APPLIED |
| AS EXISTING CAR SALES OFFICE AND EXISTING TENANT FOR |
| SAME USE. |
| |
| 6) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO |
| FS 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR |
| CODE COMPLIANCE. PLEASE SEE A FEE OF $2100.00 HAS NOW |
| BEEN ASSESSED TO THE DESIGN PROFESSIONAL AS REQUIRED |
| PER THE FLORIDA STATUTES AS GIVEN. THIS FEE IS BEING |
| ADDED TO THEEXISTING 4X FEE FOR STARTING WORK WITHOUT |
| PERMITS WHICH WAS ALREADY ADDED TO THIS JOB. PLEASE SEE |
| THIS FEE IS REQUIRED TO BE PAID BEFORE RESUBMITTING OF |
| PLANS FOR THE NEXT REVIEW. PLEASE ALSO KNOW ONE SET OF |
| EACH OF THE PLANS ARE BEING RETAINED BY THIS OFFICE. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
2007-01-06 20:09:50 | 2007-01-06 20:09:50 |
| IN ELEC FOR REVIEW |