Plan Review Notes
Plan Review Notes For Permit 06080061
Permit Number 06080061
Review Stop P
Sequence Number 2
Notes
Date Text
2006-12-07 13:54:18DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ****2ND REVIEW - FROM PREVIOUS REVIEW:
  
 1. SHT D-1 IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5. INDICATE WHERE THE
 SANITARY PIPING WILL BE ABANDONED. POINT
 OF ABANDONMENT SHALL NOT BE COVERED
 PRIOR TO INSPECTIONS.
 ****RESPONSE NOTED.DETAIL 5 DOES NOT INDICATE WHERE
 THE FLOOR DRAINS HAVE BEEN DISCONNECTED FROM THE
 BUILDING DRAIN. PLEASE INDICATE WHERE THE FLOOR DRAINS
 WILL BE DISCONNECTED.DEMO INSPECTION WILL BE
 REQUIRED.
  
 2. OK
  
 3. SHT A-5 WATER RISER DIAGRAM. THE
 WATER HAMMER ARRESTORS PROVIDED SHALL BE
 LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
 ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTORS ARE
 STILL SHOWN IN THE CEILING, NOT NEAR THE FIXTURE AS
 REQUIRED.
  
 4. SHT A-5 WATER RISER DIAGRAM. FULL
 OPEN VALVES SHALL BE INSTALLED ON THE
 TOP OF EVERY WATER DOWN-FEED PIPE.
 SECTION 606.1(4).
 ****RESPONSE NOTED, BUT THE WATER DOWN FEED PIPE TO THE
 TOILET ROOM FIXTURES DOES NOT HAVE A FULL OPEN VALVE
 INSTALLED AT THE TOP AS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]