Plan Review Notes
Plan Review Notes For Permit 06080061
Permit Number 06080061
Review Stop M
Sequence Number 2
Notes
Date Text
2006-11-02 18:49:37--------------------DENIED-----------------
  
 FBC 2004
 FBC,EB 2004
 FBC,M 2004
  
 1. PER FBC,EB SEC.609.1, PLEASE SHOW COMPLIANCE WITH
 VENTILATION REQUIREMENTS OF FBC,M SEC.402 OR 403.
  
 2. PER FBC,EB SEC.509.1 ANY COMPONENT OF THE EXISTING
 A/C SYSTEM SHOWN TO BE DEFECTIVE SHALL BE REPAIRED OR
 REPLACED - FBC,M 301.11
  
 3. CAR RENTAL AREA SHOWS NEW R/A GRILL IN CEILING WITH
 NO DUCT ATTACHED. PLAN NOTE SAYS ALL RETURNS TO BE
 DUCTED. THIS R/A GRILL MAY BE DELETED DUE TO FREE FLOW
 RETURN BACK TO THE 48X36 CENTRALIZED RETURN IN THE
 VESTIBULE.
  
 4. THE TWO 12" ROUND R/A JUMPERS DO NOT MEET THE
 BALANCED RETURN EXCEPTIONS OF FBC,M 601.4.UNLESS THE
 DUCTS ARE DESIGNED TO MEET THE EXCEPTIONS, A FIELD TEST
 WILL BE REQUIRED AT FINAL INSPECTION TO SHOW COMPLIANCE
 WITH THE MAXIMUM ALLOWABLE PRESSURE DIFFERENTIAL OF
 THIS SECTION (0.01" WC).
  
 5. PG A1 DETAIL #5 - ROOF INSULATION SHALL NOT BE
 INSTALLED ON A SUSPENDED CEILING WITH REMOVABLE CEILING
 PANELS PER FBC SEC. 13-404.1.ABC.1.SEE SEC. 13-B-1.3
 FOR INSULATION INSTALLATION REQUIREMENTS.
  