Plan Review Notes
Plan Review Notes For Permit 06080061
Permit Number 06080061
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-28 17:16:06***UNSAT 2ND REVIEW**
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES DUE TO COMPLETE CHNAGE IN THE SERVICE AS NOW
 SUBMITTED.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH NEW NOTES ADDED TO THE BOTTOM.
  
 1) NOTE:NO, SAME NOTE.
 RESPONSE MENTIONS TO SEE 6 AND 7, HOWEVER NOT COMPLETE
 FOR NEW PANEL EM AS THE LOADS ARE NOT EVEN SHOWN AND
 COULD NOT LOCATE ANY LOAD CALCULATIONS FOR SERVICE.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE PROVIDE CALCULATIONS FOR
 EXISTING SERVICE PER 220.3,220.10,220.11
 220.13 ETC
 ALL CONTINUOUS LOADS PER 215.3,230.42
  
 2) NOTE: NO/OK, RECEPTS ADDED, HOWEVER LOADS AND LOADS
 IN CALCULATIONS NOT SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.62, FOR MISSING
 SHOW WINDOWS OUTLETS REQUIRED ABOVE
 WINDOWS.
 "TO DISCOURAGE FLOOR RECEPTACLES AND
 UNSIGHTLY EXTENSION CORDS LIKELY TO
 CAUSE PHYSICAL INJURY, RECEPTACLES MUST
 BE INSTALLED DIRECTLY ABOVE A SHOW
 WINDOW, AND ONE RECEPTACLE IS REQUIRED
 FOR EVERY 12 LINEAR FT OR ?MAJOR
 FRACTION THEREOF? (6 FT OR MORE). SEE
 220.3(B)(7) AND 220.12(A) FOR
 INFORMATION REGARDING LOAD COMPUTATIONS
 FOR SHOW WINDOWS."
  
 3) NOTE:OK.
  
 4) NOTE: OK.
  
 *** NEW NOTE DUE TO COMPLETLY NEW RISER SUBMITTED. **
  
 5) NOTE: PLEASE SEE A NEW MTS PANEL IS BEING SHOWN,
 HOWEVER PLEASE SUBMIT MANUFACTURES SPACES/CUT SHEETS
 FOR THIS PANEL/ MTS.
 PLEASE SEE THIS UNIT ON RISER DOES NOT CORRELATE WITH
 THE EM AS SHOWN ON SHEET 7.
 110.3,90.7, 225.31-225.39 ETC
  
 6) NOTE: PLEASE SEE MISSING DISCONNECTING MEANS FOR
 POWER FROM GEN, OR-THE MTS IS TO BE LOCATED OUTSIDE, OR
 THERE ARE NUMEROUS OTHER SCENARIOS WHICH CAN BE DONE .
 PLEASE SEE NOTE ABOVE.
  
 7) NOTE: PLEASE SEE NOW A RISER IS BEING SUBMITTED,
 HOWEVER PLEASE LABEL AND CORRELATE ALL EQUIPMENT AND
 SIZES FROM PANELS TO RISER. PLEASE COMPLETE RISER
 DIAGRAM WITH ALL CONDUCTORS AND THE CORRECT AMOUNT.
 PLEASE SEE RISER SHOWS SEC'S, HOWEVER THE # OF
 CONDUCTORS DO NOT ADD UP???
 PLEASE SEE THE FEEDERS FOR THE PANEL "A" ARE NOT SHOWN
 ON RISER , HOWEVER NOTED ON PANEL "A" AS EXISTING 150A
 RATED?PLEASE EXPLAIN THIS AS THE RISER NOW INDICATES
 NEW 200A FUSES FEEDING THE EXISTING 150A FEEDERS.
 PLEASE COMPLETE RISER. 240.4,310.16, 215.5 ETC
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE MISPRINT FOR THE EQUIPMENT
 GROUNDING CONDUCTOR ON PANEL "EM", SHOWS #60 FOR #6.
  
 9) NOTE: PLEASE SEE COLOR CODING SHALL BE BLACK,
 ORANGE, RED. IF INDEED AS NOTED. PLEASE SEE LABELING OF
 277/480 CAN NOT BE "ORANGE" ON "B" PHASE, IF CODE
 REQUIRES ORANGE FOR A "HIGH-LEG" 277/480V SYSTEMS ARE
 NOT "HIGH-LEGS".
 PLEASE ADJUST.
 300.
  
 10) NOTE; PLEASE SHOW LOCATION OF RECEPT AND NEMA
 RATING. PLEASE SUBMIT SPEC ON RECEPT FOR WP LOCATION.
 110.3,90.7.
 FBC 106.1.2 ADMIN SECT.
  
 11) NOTE: PLEASE SEE COPY OF FS 553.80(2)(B) ATTACHED
 TO NOTED WITH RESPECT TO REPEAT COMMENTS.
 THIS IS ONLY A NOTICE GIVEN ATTHIS TIME.
  
  
 ** PLEASE KNOW, AS RISER HAS MANY COMMENTS, PLEASE
 ADDRESS ALL.
 PLEASE KNOW AS SOME INFORMATION HAS NOT YET BEEN
 SUBMITTED THERE MAY BE COMMENTS ON NEXT REVIEW.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]