2006-11-09 16:57:29 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) W P B ADMINISTRTIVE CODE 106.3.3* |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. PRODUCT APPROVALS HAVE NOT |
| BEEN APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 3)SUBMIT ENERGY CALCULATIONS AND FORMS AS REQUIRED BY |
| FBC 13-101.1.3 FOR RENOVATED COMMERCIAL BUILDINGS. |
| ADDITIONAL CONDITIONED SPACE IS BEING ADDED THAT WAS |
| PREVIOUSLY UNCONDITIONED. (2 COPIES) |
| |
| 4) ALL DOORS REQUIRED TO BE ACCESSIBLE BY FBC 11-4.1.6 |
| ARE REQUIRED TO HAVE HARDWARE WHICH COMPLIES WITH |
| 11-4.13.9. THE NOTES ON THE DOOR SCHEDULE DO NOT |
| ADDRESS ALL OF THE DOORS THAT ARE REQUIRED TO BE |
| ACCESSIBLE. |
| |
| 5) THE STOREFRONT SHOP DRAWINGS FROM THE ENGINEER |
| (THOMAS J. TWOMEY) ARE REQUIRED TO BE SIGNED AND |
| SEALED. SEE FAC 61G15-23.002 AND CHAPTER 471, F.S. |
| |
| 6) THE CODE SECTION FOR THE REQUIRED ACCESSIBLE COUNTER |
| IS INCORRECTLY LISTED AS 11-4.33. THE CORRECT SECTION |
| IS FBC 11-7.2(2). ALSO AN AUXILIARY COUNTER NOT TABLE |
| IS REQUIRED AS ONE OPTION. PLEASE CORRECT. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |