Plan Review Notes
Plan Review Notes For Permit 06080061
Permit Number 06080061
Review Stop P
Sequence Number 1
Notes
Date Text
2006-08-25 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT D-1 IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 SECTION 704.5. INDICATE WHERE THE
 SANITARY PIPING WILL BE ABANDONED. POINT
 OF ABANDONMENT SHALL NOT BE COVERED
 PRIOR TO INSPECTIONS.
  
 2. SHT A-1 CAR PREPARATION AREA DRAIN
 MAY BE REQUIRED TO CONNECT TO A SAND/OIL INTECEPTOR.
 PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL COMPLIANCE
 MANAGER. (561)
 822-2271, (561 822-2279(FAX), OR E-MAIL
 [email protected].
  
 3. SHT A-5 WATER RISER DIAGRAM. THE
 WATER HAMMER ARRESTORS PROVIDED SHALL BE
 LOCATED NEAR THE FIXTURES IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING AS
 SHOWN. PDI-WH 201 AND MANUF.
 INSTALLATION INSTRUCTIONS.
  
 4. SHT A-5 WATER RISER DIAGRAM. FULL
 OPEN VALVES SHALL BE INSTALLED ON THE
 TOP OF EVERY WATER DOWN-FEED PIPE.
 SECTION 606.1(4).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6713
 E-MAIL [email protected]