Date |
Text |
2006-08-11 00:00:00 | ***UNSAT ** |
| |
| 1) NOTE: PLEASE PROVIDE CACULATIONS FOR |
| EXISTING SERVICE PER 220.3,220.10,220.11 |
| 220.13 ETC |
| ALL CONTINUOUS LOADS PER 215.3,230.42 |
| |
| 2) NOTE: PLEASE SEE 210.62, FOR MISSING |
| SHOW WINDOWS OUTLETS REQUIRED ABOVE |
| WINDOWS. |
| "TO DISCOURAGE FLOOR RECEPTACLES AND |
| UNSIGHTLY EXTENSION CORDS LIKELY TO |
| CAUSE PHYSICAL INJURY, RECEPTACLES MUST |
| BE INSTALLED DIRECTLY ABOVE A SHOW |
| WINDOW, AND ONE RECEPTACLE IS REQUIRED |
| FOR EVERY 12 LINEAR FT OR ?MAJOR |
| FRACTION THEREOF? (6 FT OR MORE). SEE |
| 220.3(B)(7) AND 220.12(A) FOR |
| INFORMATION REGARDING LOAD COMPUTATIONS |
| FOR SHOW WINDOWS." |
| |
| 3) NOTE: PLEASE SEE ALL RECEPTS IN CAR |
| PREPARATION AREA SHALL BE GFI PROTECTED. |
| 210.8B |
| |
| 4) NOTE: PLEASE SEE THE 2002 NEC IS THE |
| CURRENT EDITION ADOPTED BY THE STATE. |
| PLEASE LIST. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |