2006-08-16 00:00:00 | BUILDING DENIED |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE 2004 EXISTING BUILDING CODE ALSO |
| APPLIES AND IS NOT NOTED ON D-1. |
| |
| 3) SPECIFY THE LEVEL OF ALTERATION FROM |
| THE EXISTING BUILDING CODE. |
| |
| 4) THE CONSTRUCT TYPE SPECIFIED ON D-1 |
| IS TYPE IV-B. UNDER THE 2004 FBC THIS IS |
| HEAVY TIMBER CONSTRUCTION. SEE FBC |
| CHAPTER 6. |
| |
| 5) SUBMIT PRODUCT APPROVALS FOR THE |
| EXTERIOR DOORS, WINDOWS, STOREFRONTS, |
| OVERHEAD DOORS. |
| PRODUCT APPROVALS SUBMITTED WITH PERMIT |
| APPLICATION AFTER OCTOBER 1, 2003 ARE |
| REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. |
| |
| 6) W P B ADMINISTRTIVE CODE 106.3.3* |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 7) SUBMIT ENERGY CALCULATIONS AS |
| REQUIRED BY FBC 13-101. |
| |
| 8) PROVIDE A BUCK DETAIL FOR THE NEW |
| OVERHEAD GARAGE DOOR. |
| |
| 9) THE EXIT LIGHT AT THE LOUNGE DOOR |
| SHOWN ON THE A6 LIGHTING PLAN IS NOT |
| SHOWN ON THE A2. |
| |
| 10) NEW ENTRANCE MUST BE ACCESSIBLE. |
| SHOW COMPLIANCE. SEE FBC 11-4.1.6 (1), |
| (2) & (3) AND 114.14. |
| |
| 11) RENTAL SERVICE COUNTER MUST COMPLY |
| WITH FBC 11-7.2. |
| |
| 12) THE HEIGHT OF THE BASE CABINETS |
| SHALL COMPLY WITH FBC 11-4.33. |
| |
| 13) DOOR HARDWARE SHALL COMPLY WITH FBC |
| 11-4.13.9. |
| |
| 14) THE INTERIOR DOOR TO THE LOUNGE MUST |
| COMPLY WITH FBC 11-4.13.6. 18" CLEAR ON |
| THE PULL SIDE OF DOOR AT LATCH. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |
| |