2006-08-15 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004, SEC. 424.2 OR |
| FBRC-2004, SEC.4101 SWIMMING POOLS: |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLUMBING PLAN REVIEW: |
| |
| 1. PLEASE CORRELATE THE 400,000 GAS |
| HEATER INDICATED ON SHEET 1 SPECIFICA- |
| TIONS WITH THE PIPING SCHEMATIC ON SHEET |
| 2. THE PIPING SCHEMATIC ON SHEET 2 DOES |
| NOT INDICATE THE GAS HEATER, PLEASE |
| INDICATE THE GAS HEATER ON THE |
| RESUMITTAL. |
| 2. PLEASE SUBMIT MANUFACTURER CUT SHEETS |
| OF THE 400,000 BTU GAS HEATER THAT |
| CONFORMS WITH THE FOLLOWING. |
| (A) FBC-2004 SEC. 424.2.14.1, OR |
| FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| SHEETS REQUIRED, PLEASE SUBMIT) |
| (B) FBC-2004 SEC. 424.2.14.2, OR |
| FBCR-2004 SEC. R4101.14.2 WATER |
| RETENTION, PROVIDE A POSITIVE MEANS OF |
| RETAINING WATER IN THE HEATER WHEN PUMP |
| IS SHUT OFF.(MANUFACTURE SHEETS |
| REQUIRED, PLEASE SUBMIT) |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |