2006-08-24 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT A-1 WOMENS AND MENS RESTROOMS |
| INDICATE ADA COMPLIANT STALLS. THESE ARE |
| NOT COMPLIANT WITH FBC-2004 CHAPTER 11 |
| SECTION 11-4.17.3 EXCEPTION (1). SEE |
| FIGURE 30E FOR CORRECT LAYOUT OF |
| REQUIRED STALL. |
| |
| 2. SHT A-4 THE FOLLOWING INFORMATION IS |
| REQUIRED FOR THE RESTROOMS: |
| FOR THE W/C'S |
| A. 11-4.16.2 CLEAR FLOOR SPACE |
| B. 11-4.16.5 FLUSH CONTROLS |
| FOR THE UNINAL |
| A. 11-4.18.3 CLEAR FLOOR SPACE |
| B. 11-4.18.4 FLUSH CONTROLS |
| FOR THE LAVS |
| A. 11-4.19.3 CLEAR FLOOR SPACE |
| B. 11-4.19.5 FAUCETS |
| |
| 3. SHT A-4 PER SECTION 1210.2 |
| WALLS WITHIN 2 FEET (610 MM) OF URINALS |
| AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE, TO A HEIGHT |
| OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND |
| EXCEPT FOR STRUCTURAL ELEMENTS, THE |
| MATERIALS USED IN SUCH WALLS SHALL BE OF |
| A TYPE THAT IS NOT ADVERSELY AFFECTED BY |
| MOISTURE. |
| PLEASE INDICATE HOW MR GYPSUM WALL BOARD |
| COMPLIES WITH THESE REQUIREMENTS. |
| |
| 4. SHT P-2 WATER ISOMETRIC. A WATER |
| HAMMER ARESTOR IS REQUIRED AT THE DISH |
| WASHER. 604.9. |
| |
| 5. SHT P-2 SANT. ISOMETRIC. SHOW ALL |
| PIPE SIZES TO THE W/C'S. SECTION |
| 106.1.1. |
| |