Date |
Text |
2006-08-14 00:00:00 | *** UNSAT *** |
| |
| 1) NOTE: PLEASE SEE NO INFORMATION FOR |
| ELEVATOR PUMP/MOTOR SIZE(S) WERE SHOWN |
| ON MDP. PLEASE SEE NO FEEDERS ARE |
| INDICATED. PLEASE ALSO COMPLETE |
| INFORMATION FOR THE DICONNECT AND SIZE |
| IN ELEVATOR EQUIPMENT ROOM. |
| PLEASE CLARIFY IF THE ELEVATOR CONTROLS |
| ARE GOING TO BE FED TO ANY FA SYSTEMS, |
| WITH SHUNT CONTROLS.620.51B |
| |
| 2) NOTE: PLEASE SEE PLANS MENTIONS |
| EXISTING PANELS AND THESE ARE LABLED. |
| PLEASE LABEL PANELS IN NEW MDP AS NEEDED |
| FOR PANELS KNOWN. PLEASE SEE NOTE ABOVE |
| AS THE ELEVATOR IS NOT INDICATED. |
| PLEASE SEE CIRCUITING ON THE MDP, AS THE |
| MDP SEEMS TO REPEAT #8,AND #9 ON THE |
| NUMERICAL IDENTIFICATION. |
| PANELS WHICH ARE NOT KNOWN , WILL BE |
| REQUIRED TO BE REVISED AT A LATER DATE |
| 408.4 |
| |
| 3) NOTE: PLEASE SEE THAT SOME SORT OF EM |
| BATTERY BACK UP FIXTURE WILL BE REQUIRED |
| IN THE NEW BATHRMS, ELEVATOR EQUIPMENT |
| RM AND THE MAIN ELECTRICAL ROOM. |
| IF EXISTING, PLEASE SHOW. |
| NFPA-101 2003 7.8, 7.9, NFPA-70 700.16, |
| 700.12E. |
| |
| 4) NOTE: PLEASE CLARIFY PLANS WHICH SEEM |
| TO ALSO LABEL THE "MAIN ELECTRICAL ROOM" |
| AS THE "ELEVATOR EQUIPMENT ROOM'? PLEASE |
| KNOW PER STATE ELEVATOR CODE, ONLY |
| ELECTRICAL EQUIPMENT PERTINENT TO THE |
| ELEVATOR EQUIPMENT IS PERMITTED IN THIS |
| RM. |
| PLEASE ALSO CLARIFY THE DOOR OR ACCESS |
| TO THE MAIN ELECTRICAL EQUIPMENT ROOM, |
| AS ELECTRICAL PLANS DO NOT APPEAR TO |
| SHOW ANY OPENING? |
| 110.26, 230.70 |
| |
| 5) NOTE: PLEASE VERIFY THE NEW OR |
| EXISTING SEC'S FOR THE NEW 800A MCB MDP. |
| IT IS UNCLEAR OF THE SIZE OF THE |
| EXISTING. |
| 240.4, 310.16. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |